Web Based Ethernet I/O Data Acquisition Module with 6 Channel Power Relay Output and 6 Channel Isolated Digital Input (Counter), communicable over Ethernet and Modbus TCP Protocol. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F). Replacement for PETL-7060.
Features
The ET-7060, a web-based Ethernet I/O module, features a built-in web server which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Remote control is as easy as you surfing the Internet.
With the web HMI function, no more programming or HTML skills are needed, so creating dynamic and attractive web pages for I/O monitoring and I/O control is as simple as it can be. The ET-7060 offers easy and safe access for users anytime, anywhere! In addition, the ET-7060 also supports the Modbus/TCP protocol that creates perfect integration between ET-7060 and SCADA software.
The ET-7060 is designed for applications in industrial monitoring and measurement; so it is created to survive harsh and rough environments. The module contains 2-way isolation from noise and surges, one for digital inputs and the other for Ethernet. The ET-7060 has got a wide range of power input (10~30VDC) and operating temperature (-25°C~+75°C).
ET-7060 comes with FREE EZ Data Logger Software.
Built In Web Server
Each ET-7060 module has a built-in web server that allows the user to easily configure, monitor and control the module from a remote location using a regular web browser.
Web HMI
The Web HMI function allows the user to create dynamic and attractive web pages to monitor and control the I/O points. The user can upload specific I/O layout pictures (bmp, jpg, gif format) and define a description for each I/O point. No HTML or Java skills are needed to create the web pages.
Specifications
Software | |
Built-In Web Server | Yes |
Web HMI | Yes |
I/O Pair Connection | Yes |
Communication | |
Ethernet Port | 10/100 Base-TX with Auto MDI/MDI-X |
Protocol | Modbus/TCP, Modbus/UDP |
Security | ID, Password and IP Filter |
Dual Watchdog | Yes, Module (0.8 second), Communication (Programmable) |
LED Indicators | |
L1 (System Running) | Yes |
L2 (Ethernet Link/Act) | Yes |
L3 (Ethernet 10/100 M Speed) | Yes |
PoE Power | - |
2 Way Isolaiton | |
Ethernet | 1500 VDC |
I/O | 3000 Vrms |
EMS Protection | |
ESD (IEC 61000-4-2) | 4 kV Contact for each terminal |
EFT (IEC 61000-4-4) | +/-2 kV for Power |
Power Requirements | |
Reverse Polarity Protectionn | Yes |
Powered from terminal block | Yes, 10 ~ 30 VDC |
Powered from PoE | - |
Consumption | 2.9 W |
Mechanical | |
Dimensions (W x L x D) | 72 mm x 123 mm x 35 mm |
Installation | DIN-Rail or Wall mounting |
Environment | |
Operating Temperature | -25 °C ~ +75 °C |
Storage Temperature | -30 °C ~ +80 °C |
Humidity | 10 ~ 90% RH, non-condensing |
I/O Specifications
Digital Input/Counter | |||
Input Channels | 6 | ||
Type | Wet Contact (Sink, Source) | ||
On Voltage Level | +10 VDC ~ +50 VDC | ||
Off Voltage Level | +4 VDC max. | ||
Input Impedance | 10 kΩ | ||
Counters | Max. Count | 4,294,967,285 (32 bits) | |
Max. Input Frequency |
500 Hz | ||
Min. Pulse Width | 1 ms | ||
Overvoltage Protection | +70 VDC | ||
Power Relay | |||
Output Channels | 6 | ||
Type | Power Relay, Form A (SPST N.O.) | ||
Operating Voltage Range | 250 VAC/30 VDC | ||
Max. Load Current | 5.0A/channel at 25 °C | ||
Operate Time | 6 ms (Typical) | ||
Release Time | 3 ms (Typical) | ||
Electrical Life (Resistive Load) |
VDE | 5A 250 VAC 30,000 ops (10 ops/minute) at 75 °C | |
5A 30 VDC 70,000 ops (10 ops/minute) at 75 °C | |||
UL | 5A 250 VAC/30 VDC 6,000 ops. | ||
3A 250 VAC/30 VDC 100,000 ops. | |||
Mechanical Life | 20,000,000 ops. at no load (300 ops./minute) | ||
Power On Value | Yes, Programmable | ||
Safe Value | Yes, Programmable |