ZT-2042
Zigbee Wireless Module with 4-channel PhotoMOS Relay Output and 4-channel Open Collector Output Digital Output, communicable over Modbus RTU protocol, and supports operating temperatures from -25 ~ +75°C (-13F ~ 167F).
References & Support
Features
The ZT-2042 offers 4 PhotoMOS relay output channels and 4 sink-type digital output channels with short circuit protection. Each channel features photo couple isolation. The ZT-2042 has 8 LED indicators to display the DO channel status. 4kV ESD protection and 3000 VDC intra-module isolation are the standard. Users can easily configure the module address, protocol, checksum, ZB-PID and ZB-channel settings using a combination of rotary and DIP switches.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
Specifications
I/O Specifications
Relay Output | |
Output Channels | 4 |
Output Types | PhotoMOS Relay, Form A |
Load Voltage | 60 VDC/VAC |
Max. Load Current | 60 V/1.0 A (Operating Temperature: -25 ~ +40°C) |
60 V/0.8 A (Operating Temperature: +40 ~ +60°C) | |
60 V/0.7 A (Operating Temperature: +60 ~ +75°C) | |
Power-on Time | 5.0 ms |
Power-off Time | 0.5 ms |
Digital Output | |
Output Channels | 4 (Sink) |
Output Types | Isolated Open Collector |
Max. Load Current | 700 mA/channel |
Load Voltage | +5 VDC ~ +50 VDC |
Power-off Time | 0.5 ms |
External Power Reversed Protection and Short Circuit Protection |
Yes |
Current Limited Protection | 1.1 A |
System Specifications
Communication Interface | ||
Wireless Standards | ZigBee 2007 Pro | |
Transmission Power | 11 dBm (FCC Certificated) ( Max 19 dBm) | |
2.4 GHz Antenna | 5 dBi Omni directional | |
Transmission Range (LoS) | 700 m (Typical) | |
Certification | CE/FCC, FCC ID | |
Max. Slaves in a ZigBee Network | 255 | |
ZB-100R/ZB-100T Support | - | |
Protocols | Supports DCON and Modbus RTU Protocols | |
Hot Swap | Rotary and DIP switch | |
LED Indicators | ||
Power | 1 LED, Red | |
ZigBee Communication | 1 LED, Green | |
Digital Output | 8 LEDs, red | |
Isolation | ||
Intra-module Isolated, Field-to-Logic |
3000 VDC | |
EMS Protection | ||
ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
|
EFT (IEC 61000-4-4) | 4 kV for Power | |
Surge ( IEC 61000-4-5) | 3 kV for Power | |
Power | ||
Power Consumption | 1.32 W Max. | |
Mechanical | ||
Flammability | Fire Retardant Materials (UL94-V0 Level) | |
Dimensions (W x L x H) | 33 mm x 87 mm x 107 mm | |
Installation | DIN-Rail | |
Environment | ||
Operating Temperature | -25 ~ +75°C | |
Storage Temperature | -30 ~ +80°C | |
Relative Humidity | 10 ~ 90% RH, Non-condensing |