User-defined I/O Expansion PoE Module, web browser configurable, allows users to implement IF-Then Else If type control logic and communicable over Modbus TCP. MiniOS7 Operating System.

WISE-7901

User-defined I/O Expansion PoE Module, web browser configurable, allows users to implement IF-Then Else If type control logic and communicable over Modbus TCP. MiniOS7 Operating System.

  Price:  $389.00  

Features

Introduction

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-7901 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7901 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.

This module WISE-7901 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D, D/A according to the using X-Board.

Features

  • Built-in Web Server for IF-THEN-ELSE rule setting
  • Built-in IF-THEN-ELSE rule engine for logic operation
  • No more programming. Just click and get done!
  • Support IO, Counter, Timer, Email operations
  • Modbus/TCP Protocol for SCADA Software Seamless Integration
  • IEEE 802.3af-compliant Power over Ethernet (PoE)
  • 10/100 Base-TX Ethernet
  • I/O expansion bus
  • Support DI/DO X-Boards: X107, X109, X110, X111
  • Support Multi-Function X-Boards: X202, X203, X303, X304, X305, X308, X310, X324

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

Specifications

Hardware Specifications

Model
WISE-7901
WISE-7901D
CPU Module
CPU 80186 or compatible (16-bit and 80 MHz)
SRAM 512 KB
Flash 512 KB; Erase unit is one sector (64 K bytes); 100,000 erase/write cycles
EEPROM 16 KB
NVRAM 31 Bytes (battery backup, data valid up to 10 year)
OS MiniOS7
RTC
(Real Time Clock)
RTC Provide seconds, minutes, hours, date of week/month; month and year, valid from 1980 to 2079
64-bit Hardware Serial Number Yes
Watchdog Timers Yes (0.8 second)
Communication Ports
Ethernet RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators)
COM 1 RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max.
COM 2 RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed: 115200 bps max.
LED Indicators
System LED Yes 
LED Display - 5-digit 7-segment LED display
Special Indicator PoE LED
Hardware Expansion
I/O Expansion Bus Yes, 1
Mechanical
Dimensions
(W x H x D)
72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Ambient Relative Humidity 10 ~ 90% RH, non-condensing
Power
Protection Power reverse polarity protection
Frame Ground Yes (for ESD Protection)
Input Range +12 ~ +48 VDC
Power over Ethernet (PoE) IEEE 802.3af Class 1
Power Consumption 2.0 W 3.0 W

Software Specifications

Functions
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators
3 THEN actions
3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions.
12 Schedules Setup prescheduled routine tasks.
12 Emails Send Email messages to pre-set Email receivers.
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
Modbus/TCP Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions
DI Channel ON、OFF、ON to OFF、OFF to ON、Change
AI Channel =、>、<、>=、<=(value)
Internal Register
DI Counter =、>、<、>=、<=(value)、Change
DO Counter
Timer Timeout、Not Timeout
Schedule In Range、Out Range
THEN / ELSE Actions
DO Channel ON、OFF、Pulse Output
AO Channel Change the value
Internal Register
DI Counter Reset
DO Counter
Timer Start、Stop
Schedule
Email Send

Related Products


ICP DAS USA,Inc.