Features
Ethernet pairs. In addition, WISE-7517M-10 also has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.
By integrating with IF-THEN-ELSE rule engine, WISE-7517M-10 provides powerful functions such as I/O Monitoring/Control, Counter, Timer, Schedule, E-mail sending & CGI Command sending for use in various industrial applications. WISE-7517M-10 also supports Modbus TCP and MQTT protocols to make seamless integration with SCADA, IT and IoT (Internet of Things) system.
- Runs on browsers, no extra software tool is required.
- No more programming, Web pages provided for control logic editing.
- IF-THEN-ELSE logic rules execution ability.
- Built-in I/O (AI: 10/20 Channels)
- Support I/O Moniitoring/Control, Counter, Timer, Schedule, Email sending and CGI Command sending operations.
- Modbus TCP Protocol for SCADA System Integration.
- IEEE 802.3af-compliant Power over Ethernet (PoE).
- 2-port Ethernet Switch for Daisy-Chain Topology.
- MQTT Protocol for IT & IoT (Internet of Things) System Integration.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Specifications
Analog Input
Channels
10 differential or 20 single-ended (Note1), software selectable
Type
±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V
±20 mA ,0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
Resolution
16-bit
Sampling Rate
10 Samples/Second (Total)
Accuracy
±0.1 %
Zero Drift
±20 μV/°C
Span Drift
±25 ppm/°C
Overvoltage Protection
Differential
240 Vrms
Single-ended
150 Vrms
Common Voltage Protection
±200 VDC
Overcurrent Protection
Yes, 50 mA at 110 VDC
Virtual Channel to Channel Isolation
Yes, 400 VDC
Open Wire Detection for 4 ~ 20 mA
Yes
Input Impedance
Voltage
2 MΩ (Differential), 1 MΩ (Single-ended)
Current
125Ω
Common Mode Rejection
86 dB Min.
Normal Mode Rejection
100 dB
Note1: Differential mode can be used for voltage input and current input. Single-Ended mode can be used for voltage input only.
Communication
Ethernet Port
2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE
Yes
Protocol
Modbus TCP, MQTT
LED Indicators
for System Running
Yes
for Ethernet Link/Act
Yes
for I/O Channel Status
Yes
for PoE Power
Yes
2-Way Isolation
I/O
2500 VDC
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for Each Terminal and
±8 kV Air for Random Point
EFT (IEC 61000-4-4)
±2 kV for Power Line
Surge (IEC 61000-4-5)
±2 kV for Power Line
Power
Reverse Polarity Protection
Yes
Powered from Terminal Block
12 ~ 48 VDC
Powered from PoE
Yes, IEEE 802.3af, Class1
Consumption
3.7 W (Max.)
Mechanical
Dimensions (L x W x H)
120mm x 97mm x 42mm
Installation
Wall mounting
Environment
Operating Temperature
-25 °C ~ +75 °C
Storage Temperature
-30 °C ~ +80 °C
Humidity
10 ~ 90% RH, non-condensing
Software Specifications
Functions
Rule Configuration Website
Access Web server on WISE controllers to edit and upload logic rules through web browser.
72 IF-THEN-ELSE Logic Rules
3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers
Hold temporary variables and read/write data.
24 Timers
Delay / Timing functions.
24 Schedules
Setup prescheduled routine tasks.
24 Emails
Send Email messages to pre-set Email receivers.
24 CGI Commands
Send pre-set CGI commands.
24 Recipes
Set up THEN/ELSE action groups.
8 P2P remote modules
Set up the connection information for the remote WISE modules.
Modbus/TCP Protocol
Real time control and monitoring I/O channels and system status of controllers via SCADA software.
MQTT Protocol
Real time message publish/subscribe mechanism for I/O channels and system status via IT/IoT software.
IF Conditions
AI Channel
=, >, <, ≥, ≤ (value)
Internal Register
=, >, <, ≥, ≤ (value)
Timer
Timeout, Not Timeout
Schedule
In Range, Out of Range
P2P
DI, AI, DI counter, DO counter, IR
Rule Status
Enable, Disable
THEN / ELSE Actions
Internal Register
Change the value
Timer
Start, Reset
Schedule
Enable, Disable
Send
MQTT message
Send
CGI Commands
Send
Recipe
Execute
P2P
DO(On/Off), AO, IR
Rule Status
Enable, Disable