WISE-7151
Data acquisition controller with 16-channel Isolated Digital Input (16-bit Counter),Power-over-Ethernet (PoE) function and easy web configuration, can send Email alarms based on configurable conditions and allow users to implement IF-Then-Else type control logic. Communicable over Modbus TCP. MiniOS7 Operating System. Supports operating temperatures of -25 °C ~ +75 °C (-13F ~ 167F).
Features
WISE (Web Inside, Smart Engine) is an easy-to-use controller for use in remote monitoring and control, building automation, industrial automation, remote maintenance and testing applications. WISE offers a user-friendly web interface that allows users to implement control logic like IF-THEN-ELSE with just a few clicks; no programming is needed. By connecting with other data acquisition I/O's, the smart WISE controller can automatically send Email alarms to users based on configurable conditions. For example, in a tank monitoring application, the controller can be set to send out Email alarms to related personnel if the tank level goes beyond the preset level. The simple user interface can help users improve their productivity and reduce their operational costs.
WISE-7151 follows IEEE 802.3af-compliant (classification, Class 1) Power-over-Ethernet (PoE) specification. It can be powered by the PoE Ethernet port, which adds more flexibility and higher efficiency for users. In this way, it can simply the system design, save space, reduce cables and costs. In case of a non-PoE environment, WISE-7151 controller can also be powered by auxiliary power sources like AC adapters or battery, etc.
The WISE-7151 controller communicates over Modbus TCP protocol to easily integrate with SCADA software available. It features 16-channel isolated wet contact digital inputs. Each digital input channel supports counter input.
- Can send Email and SMS alarms to users based on configurable conditions
- Built-in web server for easy configuration
- Built-in IF-THEN-ELSE rule engine for logic control
- No programming skills needed. Configuration can be done on a regular web browser with a few clicks.
- Supports IO, Counter, Timer, Email operations
- Communicates over Modbus TCP and can integrate with Modbus I/O's and SCADA Software.
- Comply with IEEE 802.3af Power over Ethernet (PoE) standard
- Equipped with 10/100 Base-TX Ethernet port
- 2-way Isolation/ESD Protection
- 16 Wet Contact (Sink, Source) digital input
Specifications
Digital Input | ||
Input Channels | 16 | |
Input Type | Wet Contact (Sink, Source) | |
On Voltage Level | +10 VDC ~ +50 VDC | |
Off Voltage Level | +4 VDC Max. | |
Input Impedance | 10 kΩ | |
Counters | Max. Count | 65535 (16 bits) |
Max. Input Frequency | 50 Hz | |
Min. Pulse Width | 10 ms | |
Overvoltage Protection | +70 VDC | |
System | ||
CPU | 80186 CPU (80 MHz) | |
SRAM | 512 KB | |
Flash Memory | 512 KB | |
EEPROM | 16 KB | |
Dual Watchdog | Yes | |
Communication | ||
PoE Ethernet Port | 10 / 100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X | |
2 Way Isolation | ||
I/O | 3000 Vrms | |
Ethernet | 1500 VDC | |
EMS Protection | ||
ESD (IEC 61000-4-2) | 4 kV Contact for each terminal | |
EFT (IEC 61000-4-4) | +/-2 kV for Power | |
LED Indicators | ||
PoE | PoE On | |
L1 | System Running | |
L2 | Ethernet Link/Act | |
L3 | Ethernet 10/100M Speed | |
Power Requirements | ||
Required Supply Voltage | Powered by Power-over-Ethernet (PoE) or auxiliary power +12 ~ +48 VDC (non-regulated) | |
Powered from PoE | Yes, IEEE 802.3af, Class1 | |
Power Consumption | 0.12 A @ 24 VDC Max. | |
LED Indicator | Yes | |
Mechanical | ||
Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm | |
Installation | DIN-Rail or Wall mounting | |
Environment | ||
Operating Temperature | -25 °C ~ +75 °C | |
Storage Temperature | -30 °C ~ +80 °C | |
Humidity | 5 ~ 90% RH, non-condensing |
Software Specifications
Functions | |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Emails | Send Email messages to pre-set Email receivers. |
Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions | |
DI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
Internal Register | =、>、<、>=、<=(value) |
DI Counter | =、>、<、>=、<=(value)、Change |
Timer | Timeout、Not Timeout |
THEN / ELSE Actions | |
DO Channel | ON、OFF、Pulse Output |
Internal Register | Change the value |
DI Counter | Reset |
Timer | Start、Stop |
Send |