I-87H17W
8-channel HART Current Input Module. I-87H17W is phased out and replaced by HRT-710, HRT-310 and HRT-711.
Features
The I-87H17W has officially been phased out and will no longer be available. It has now been replaced by HRT-710, HRT-711, and HRT-310.
The I-87H17W is a HART analog input module. It can measure 4~20mA current and act as a HART master, allowing communication with HART field devices. Its user-friendly design saves a lot of work when measuring current due to a built-in resistor. Now, users can measure current directly without any external resistor. The sampling rate of I-87H17W is changeable and supports DCON protocol. Otherwise, ICP DAS also provides API library for users to develop their own program by VC,VB , C# or VB.Net environment.
Application
Current Measuring, Petrochemical Industry Application, Environment Monitoring, Tunnel Monitoring, Building Monitoring etc.
Features
- Analog input capability with or without HART
- Real-time HART data acquisition
- Full read/write access to all device information
- Support 4 ~ 20 mA current input
- 2 or 4 wire transmitters of HART
- With a built-in resistor
- Open wire detection
- 4 kV ESD protection
- 2500 VDC intra-module isolation
- Built-in Watchdog
- RoHS compliance
- Support DCON Protocol
- Provide API library and demos
- Support XPAC, WinPAC, iPAC, I-87Kx,RU-87Px, USB-87Px, ET-87Px series
Specifications
Analog Input |
|
Input Channels |
8 Differential 4-20 mA input channels |
HART Wiring |
2 or 4 wire transmitters |
HART Response Time |
1s per single channel |
Resolution |
16-bit |
Zero Drift |
+/- 20μV/ °C |
Span Drift |
+/- 25μV / °C |
Common Mode Rejection |
86 dB |
Normal Mode Rejection |
100 dB |
Input Impedance |
400 Ohms |
Common Voltage |
-200V to +200V |
Open Wire Detection |
Yes |
4KV ESD Protection |
Yes, Contact for each terminal. |
Intra-module Isolation, Field to Logic |
2500VDC |
Watchdog |
|
Dual Watchdog |
Yes, Module(1.6 sec) and Communication(Programable) |
LED |
|
LED Display |
1 LED as Power Indicator 8 LED as HART Communication Indicator |
Power |
|
Power Consumption |
Maximum : 1.8W |
Mechanism |
|
Dimensions |
30mm x 102mm x 115mm(W x L x H) Detail |
Environment |
|
Operating Temperature |
-25 to 75 °C |
Storage Temperature |
-30 to 75 °C |
Humidity |
5 to 95% RH, non-condensing |