I-7050AD
7 Channel Digital Input (Counter) and 8 Channel Digital Output Data Acquisition Module, Source Version communicable over RS-485 with display. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°).
Features
I-7050AD is intelligently designed to provide signal conditioning system monitoring and safe value settings. I-7050AD is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7050 Digital Input/Output modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
Specifications
Digital Input | |
Channels | 7 |
Input Type | Sink, non-isolated channel with common ground |
Off Voltage Level | +1V max. |
On Voltage Level | +4V ~ +30V |
Input Impedance | 3K9, 0.3W |
Counters | channels : 7 |
Max. Counts: 16-bit (65535) | |
Max. Input Frequency : 100Hz | |
Min. Pulse Width : 5ms | |
Digital Output | |
Channels | 8, Source, PNP |
Output Voltage | 30V max. |
Output Current | 50mA max. |
Interface | |
Interface | RS-485 |
Format | N, 8, 1 |
Baud Rate | 1200 ~ 115200bps |
LED Display | |
1 LED as Power/ Communication indicator | |
7 LEDs as Digital Input indicators, and 8 LEDs as Digital Output indicators (for I-7050AD) | |
Power | |
Input Voltage Range | 10~30VDC |
Power Consumption | 0.5W (I-7050A) / 1.4W (I-7050AD) |
Environment | |
Operating Temperature | -25 to 75°C |
Storage Temperature | -40 to 85°C |
Humidity | 5 to 95% RH, non-condensing |