WISE-5801-MTCP
User-defined I/O & Data Logger 16-bit Module with SMS Function for Modbus TCP Devices (RS-232, RS-485, Ethernet) 2 W Power consumption. Has operating temperature range of -25°C ~ +75°C (-13°F ~ +167°F). WISE-5801-MTCP is phased out and replaced by WISE-5231M-4GE.
Features
The WISE-5801-MTCP has officially been phased out and will no longer be available. It has now been replaced by WISE-5231M-4GE.
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS USA, Inc. that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the labor and cost spent on system development.
An I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board is supported by the WISE-5801-MTCP. In addition, WISE-5801-MTCP also supports Modbus TCP slave devices. Based on the connection ability with Modbus TCP slave devices, WISE-5801-MTCP can provide user more flexibility in application field.
WISE-5801-MTCP supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It includes all advantages which WISE series controllers can provide. In addition, WISE-5801-MTCP provides data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. WISE-5801-MTCP also features SMS sending function for alarm report and SMS command receiving function. All setting can be completed through browser.
- Built-in Web Server for IF-THEN-ELSE
- Built-in IF-THEN-ELSE rule engine for logic operation
- Support I/O, Counter, Time, Schedule, Email, Recipe operation
- No more programming. Just click and get done!
- Data logger and data files send back function supported
- Modbus TCP/RTU Protocol for SCADA Software Seamless Integration
- Support XW-Board
- Support Modbus TCP Slave Devices (Up to 7)
- SNTP Time Synchronization Supported
- Support SMS (GSM: Quad-band 850/900/1800/1900 MHz)
Specifications
System |
|
CPU |
16-bit CPU |
SRAM |
768 KB |
Flash |
512 KB |
MicroSD Expansion |
Support 1/2/4 GB microSD |
RTC (Real Time Clock) | Provide second, minute, hour, date of week, month and year |
Watchdog |
Yes |
Communication Ports |
|
Ethernet | RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X) |
COM 1 |
RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max. |
COM 2 |
RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max. (Reserved) |
LED Indicators |
|
System LED |
Yes (Red) |
Ethernet Link LED |
Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received) |
Hardware Expansion |
|
I/O Expansion Bus |
Yes |
SMS Function |
|
Frequency Band |
Quad-band 850/900/1800/1900 MHz |
Mode |
Text and Unicode mode |
Power Requirements |
|
Protection | Power Reverse Polarity Protection |
Frame Ground | Yes (for ESD Protection) |
Input Range | 12 ~ 48 VDC |
Redundant Power Input | Yes |
Power Consumption | 2.0 W; Data Link: 150 ~ 400 mA (peak) @ 24 VDC |
Mechanical |
|
Dimensions (W x H x D) |
91 mm x 132 mm x 52 mm |
Installation |
DIN-Rail |
Environment |
|
Operating Temperature |
-25°C ~ +75° (-13°F ~ +167°) |
Storage Temperature |
-30°C ~ +80°C (-22°F ~ +176°F) |
Ambient Relative Humidity |
10 ~ 90% RH (non-condensing) |
Software Specification
Functions |
|
Rule Configuration Website |
Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules |
3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers |
Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers |
Delay / Timing functions. |
12 Schedules | Setup prescheduled routine tasks. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 SMS | Send SMS to pre-set mobile phone numbers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Recipes | Set up THEN/ELSE action groups |
Data Logger | Set up the Data Logger configuration, include the data record format, and data file sending operation. |
Modbus TCP/RTU Protocol |
Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
|
DI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
AI Channel | =、>、<、>=、<=(value) =、>、<、>=、<=(value)、Change |
Internal Register | |
DI Counter | =、>、<、>=、<=(value)、Change |
Timer | Timeout、Not Timeout |
Schedule |
In Range、Out of Range |
Rule Status |
Enable、Disable |
THEN / Else Actions |
|
DO Channel | ON、OFF、Pulse Output (apply to XW-Board only) |
AO Channel | Change the value |
Internal Register | |
DI Counter | Reset |
Timer | Start、Reset |
Schedule | Enable、Disable |
Send | |
SMS | |
CGI Commands |
|
Recipe | Execute |
Data Logger | Start、Stop、One-Time Log |
Rule Status |
Enable、Disable |