Free PC Based Data Logging Software that can be Applied to Small Remote I/O Systems with up to 64 I/O tags
Features
** To get a FREE license key, click get free license key above under product reference and support **
EZ Data Logger is a small data logger software. It can be applied to small remote I/O system. With its user-friendly interface, users can quickly and easily build a data logger software without any programming skill.
Advanced EZ Data Logger is our Easy to use Data Logging Software for Advanced Applications. It supports up to 1024 I/O tags, 10 SMS or E-mail alarm contacts, up to 10 web cameras, and up to 256 virtual channels.
Easy to Use
Configurable Control and Monitoring Software
No Programming Needed
Database Can be Exported to Excel or CVS
Can Send Alarms by SMS Text Message or Email
Specifications & Additional Information
Communication
Protocols
DCON, Modbus RTU, Modbus ASCII, and Modbus TCP
Control & Logic
Virtual Channel Definition
The user can easily consolodate data into a virtual channel by tagging channel names. For example: VC3 = (AI_2 + AI_3) / 2
Control Logic (VB Script)
The user can edit the script to set the output values or to calculate data into virtual channels. You can set the channel values by channel tag names. For example: If AI_2 > 50 then DO_3=1
Alarm Notifier (by sending SMS or E-mail)
The user can link a cell phone number and email address with the data logger values. When the channel value is over the alarm value, or when the value goes back to normal, the messenger will send an SMS message (using GSM Modem with PDU mode supported) or by E-mail (using ethernet).
Value Conversion
Set gain and offset can convert analog values from volt or amp unit to another physical measurement unit.
This includes using a calculating function(using 2 points to calculate the gain and offset).
For example: rpm for rotation, kg for weight.
Configuration
No Programming Needed!
All operations are done by the click of a mouse and entering values.
Flexible module configuration
Each module and I/O point can be set to a different description and color.
Flexible workgroup configuration
Each channel can be assigned to a workgroup for easier organization.
Module Search
The user can search for DCON and M7000 serial modules -
For DCON modules,7000, 87K, 8000 modules can be searched.
For Modbus RTU modules,M7000 serial modules can be searched and can automatically set the gain and offset.
High/Low alarm with audio warning
Each AI channel can have its own high/low limit. Once the AI value over high limit or below low limit, the alarm light will be triggered with audio. The alarm status will keep warning until the user switches off the alarm light.
Views
Real time data trend (with zoom in and zoom out)
Each trend line can store more than 86400 records. Using this, you can visualize your data on a graph.
Layout view
The user can set a background picture and drag-and-drop I/O points to mapping locations. User can also change the visual channel layout object as Linear Gauge, Angular Gauge, Toggle, Number LED...
IP Camera Viewer
The user can add an IP camera's web address, and then add it to group. Then the layout display will show the web page in a sub window.
Access database supported
The database can be exported to an Excel file or CVS file.
Print Reports
The user can print reports from the trend line or data from the database.
Registration with product serial number, PC ID Code, and personal information to get a license key.
Each product serial number can request 3 license keys for 3 PC. Get License Key
Devices with Modbus RTU, Modbus Ascii, Modbus TCP protocols
Limitations:
Most 32 channels for each work group (256 for Advanced Edition)
One ICPDAS Modbus device to active all modbus drivers
Related Products
I-7019R 8 Channel Universal Analog Input Data Acquisition Current Module with High Voltage Protection, communicable over RS-485, and FREE EZ Data Logger Software. Voltage Range: ± 15mV, ± 50mV, ± 100mV, ± 150mV, ± 500mV, ± 1V, ± 2.5V, ± 5V, ± 10V. Current Range: ± 20mA. Thermocouple Types: J, K, T, E, R, S, B, N, C, L, M, L2 More Info
ET-7017-10 10/20 Channel Voltage & Current Analog Input Data Acquisition Module with High Voltage Protection and 4 digital outputs, communicable over Ethernet and Modbus TCP Protocol More Info
I-7018Z 10 Channel Voltage & Current Thermocouple Input Data Acquisition Module with High Accuracy, High ESD Protection, communicable over RS-485, FREE EZ Data Logger Software and short cable More Info
ET-7042 16-channel Sink Type Open Collector Isolated Digital Output Data Acquisition Module, communicable over Ethernet and Modbus TCP Protocol More Info
M-7015 6 AI Channel RTD Input Data Acquisition Module, communicable over Modbus RTU and RS-485 More Info
M-7018 8 Channel Voltage & Current Thermocouple Input Data Acquisition Module, communicable over Modbus RTU and RS-485 More Info
M-7017 8 Channel Voltage & Current Analog Input Data Acquisition Module. Communicable over Modbus RTU and RS-485
More Info
I-87005W 8-channel thermistor input and
8-channel digital output module More Info