M-7022
2 Channel Current Output, Voltage Output, and Analog Output Data Acquisition Module. Communicable over Modbus RTU and RS-485. Supports operating temperatures between -25°C to 75°C (-13°F ~ +167°F).
Features
The M-7022 device is a network data acquisition and control modules that support Modbus RTU. They can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/ HMI software and PLCs. Photo-isolation: 3750 Vrms
Specifications
Analog Output | |
Output Channels | 2, Channel to channel isolation |
Output Type | 0 ~ 20 mA , 4 ~ 20 mA, 0 ~ 5 V and 0 ~ 10 V |
Resolution | 12-bit |
Accuracy | +/-0.1% of FSR |
Read Back Accuracy | +/-1% of FSR |
DA Output Response Time | 10ms per channel |
Zero Drift | Current output : +/-0.2uA/°C Voltage output : +/-30uV/°C |
Span Temperature Coefficient | +/-25ppm/ °C |
Programmable Output Slope | 0.125 to 1024 mA/ second 0.0625 to 512 V/ second |
Current load resistor | Internal power : 500 ohms External 24V : 1050 ohms |
Intra-module Isolation, Field to Logic | 3000 VDC |
Interface | |
Interface | RS-485 |
Format | N, 8, 1 |
Baud Rate | 1200 ~ 115200bps |
LED Display | |
1 LED as Power/ Communication indicator | |
Power | |
Input | +10 to +30 VDC |
Power Consumption | 3.0W |
Protocol | |
Support Modbus and DCON Protocol | Yes |
Environment | |
Operating temperature | -25 to 75°C |
Storage temperature | -40 to 85°C |
Humidity | 5 to 95% RH, non-condensing |