8-channel High Voltage Input & Analog Input Data Acquisition Module communicable over Modbus RTU and RS-485. Supports input types +/-50V and +/-150V DC.  Supports operating temperatures between -25 to 75°C.

M-7017R-A5

8-channel High Voltage Input & Analog Input Data Acquisition Module communicable over Modbus RTU and RS-485. Supports input types +/-50V and +/-150V DC. Supports operating temperatures between -25 to 75°C.

  Price:  $419.00  

Features

The M-7017R is an 8-channel analog input module with an extremely high quality protection mechanism where the overvoltage protection is 240 Vrms. The input type includes both voltage and current. The M-7017R is an upgraded version of the M-7017, with the only difference being that the M-7017R is much more suitable for critically harsh environments. The sampling rate of the M-7017R is adjustable, meaning that either fast mode or normal mode can be selected. The M-7017R also has 4 kV ESD protection as well as 3000 VDC intra-module isolation. The M-7017R-A5 is an 8-channel analog input module that is especially designed for high voltage input, and has an input range of between -50 V ~ +50 V or -150 V ~ +150 V.

M-7017 solar

Specifications

Analog Input
Input Channels 8
Input Type +/-50V, +/-150V DC
Resolution 16-bit (Normal Mode) / 12-bit (Fast Mode)
Sampling Rate 10 samples/ second (Normal Mode) total
50 samples/ second (Fast Mode) total
Accuracy +/-0.1% of FSR(Normal Mode) or better
+/-0.25% of FSR (Fast Mode) or better
Band Width 15.7Hz (Normal Mode)
78.7Hz (Fast Mode)
Zero drift +/-20uV/°C
Span drift +/-25ppm/°C
Input Impedance 290K Ohms
Common Mode Rejection 86dB min.
Normal Mode Rejection 100dB
Over Voltage Protection 200 V DC
4KV ESD Protection Yes
Intra-module Isolation, Field to Logic 3000 VDC
Interface
Interface RS-485
Format N, 8, 1
Baud Rate 1200 ~ 115200bps
LED Displays
1 LED as Power/ Communication indicator
Power
Input +10 to +30 Vdc
Power Consumption 1.7W
Protocol
Support Modbus and DCON Protocol Yes
Watchdog Yes, Module, Communication (Programmable over DCON) firmware version B300 and later
Environment
Operating temperature -25 to 75°C
Storage temperature -40 to 85°C
Humidity 5 to 95% RH, non-condensing