I-87018Z (High Over Voltage Protection)
8 Channel Thermocouple Input Module. I-87018BL has Broken Line Detection. I-87018R is the Robust Power version. I-87018Z is phased out and replaced by I-87018ZW-G/S.
References & Support
Features
The I-87018Z has officially been phased out and will no longer be available. It has now been replaced by I-87018ZW-G/S.
I-87018/R has a serial bus (RS-485) communication interface with DCON protocol. It can be plugged into our WinCon, LinCon, I-8000 controllers and I-87K, RF-87K I/O expansion units. I-87018/R is a Thermocouple Input Module with 8 channels. I-87018/R is a serial cartridge based I/O module that offers the ultimate in cost effective flexibility.
Specifications
- Serial I/O Module
- Analog Input Channels: 8
- Differential Input
- Input Type: thermocouple, mV, V, or mA
- Voltage range: ± 15mV, ±50mV, ±100mV, ±500mV, ±1V, ±2.5V
- Current range: ±20mA
- Sampling rate: 10 samples/sec
- Bandwidth: 13.1 Hz
- Accuracy: ±0.05% or better
- Zero drift: ± 0.033 ppm/°J
- CMR @ 50/60 Hz: 150 dB
- NMR @ 50/60 Hz: 100 dB
- Span drift: 25ppm/°J
- Over voltage protection: ±35V
Type | Range°C |
J | -210~ +760 |
K | -270~+1372 |
T | -270~+400 |
E | -270~+1000 |
R | 0~+1768 |
S | 0~+1768 |
B | 0~+1820 |
N | -270~1300 |
C | 0~2320 |
L | -200~+800 |
M | -200~+100 |
L2(DIN43710) | -200~+900 |