I-7024R
4-channel 14-bit Analog Output, (Voltage Output and Current Output), and 5-channel Current Digital Input Module, communicable over RS-485. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).
Features
I-7024R is a RS-485 interface module and offers 4-channel analog outputs and 5-channel digital inputs. It provides programmable analaog outputs are 14-bit with 0 ~ 5 V, +/-5 V, 0~10 V, +/-10 V, 0 ~ 20 mA and 4 ~ 20 mA. And Its each terminal supports 4 kV ESD protection. And I-7024R improves better output quality in radiate environment.
Features
- 4-channel Analog Output
- 5-channel Dry Contact Digital Input
- 4 kV ESD Protection
- Dual Watchdog
- Power On Value Setting
- Safe Value Setting
- 3000 VDC Intra-Module Isolation
- A Wide Range of Operating Temperature: -25 °C~ 75 °C
- RoHS Compliance
Applications
- Industry automation
- Industrial Machinery
- Building Automation
- Food & Beverage
- Semiconductor Fabrication
- Control System
Specifications
Analog Output | |
Output Channels | 4 |
Output Type | 0 ~ 20 mA, 4~20 mA, 0 ~ 5 V, +/-5 V, 0 ~ 10 V, +/-10 V |
Resolution | 14-bit |
Accuracy | +/-0.1% of FSR |
Zero Drift | Voltage output : +/-30 μV/°C |
Current output : +/-0.2 μA/°C | |
DA Output Response Time | 10 ms per channel |
Span Temperature Coefficient | +/-20 ppm/ °C |
Programmable Output Slope | 0.125 to 2048 mA/second 0.0625 to 1024 V/second |
Voltage Output Capability | 20 mA@10 V |
Current Load Resistance | External +24 V power : 1050 Ohms |
Intra-module Isolation, Field to Logic | 3000 VDC |
Digital Input | |
Input Channels | 5 |
Input Type | Dry Contact, Source |
Contact Level | Off Voltage Level : Open |
On Voltage Level : Close to GND | |
Counters | Max. Counts : 16-bit (65535) |
Max. Input Frequency : 50 Hz | |
Min. Pulse Width : 10 ms | |
Interface | |
Interface | RS-485 |
Format | N, 8, 1 |
Baud Rate | 1200 ~ 115200 bps |
LED Display | |
1 LED as Power/Communication indicator | |
Power | |
Input | +10 ~ +30 VDC |
Power Consumption | 3.2 W max. |
EMS Protection | |
ESD (IEC 61000-4-2) | 4 kV contact for each channel |
RS (IEC 61000-4-3) | 3V/m |
Environment | |
Operating Temperature | -25 °C ~ +75 °C |
Storage Temperature | -40 °C ~ +85 °C |
Humidity | 10 ~ 90% RH, non-condensing |