ET-7052
8-channel Digital Output Isolated Source Type Open Collector Output and 8-channel Isolated Digital Input Data Acquisition Module with 32-bit Counters, communicable over Ethernet and Modbus TCP Protocol. Digital Input is Wet Contact (Sink, Source) and Digital Output is Source, Open Collector. On Voltage Level is +10 to 50VDC and Output Voltage is +10VDC to 40VDC. Supports operating temperatures between -25°F to 75°C (-13°F ~ 167°F).
Features
The ET-7052, a web-based Ethernet I/O module, features a built-in web server which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Remote control is as easy as you surfing the Internet.
No programming in HTML is needed when using HMI's functions; creating dynamic and attractive web pages for I/O monitoring and I/O control is made simple in the HMI software. The ET-7052 offers easy and safe access for users from anytime and anywhere!
The ET-7052 also supports Modbus/TCP protocol that makes perfect integration for ET-7052 to SCADA software.
The ET-7052 is designed for applications to industrial monitoring and measurement; therefore, we have made it toughly enough to survive the harsh and rough environment. The module contains 2-way isolation from noise and surges, one for digital inputs and the other for Ethernet. The ET-7000 has got a wide range of power input (10~30VDC) and operating temperature (-25°C~+75°C).
ET-7052 comes with FREE EZ Data Logger Software.
Specifications
| CPU | |
| CPU | 80186 CPU (80MHz) |
| SRAM | 512K Bytes |
| Flash Memory | 512K Bytes |
| EEPROM | 16K Bytes |
| Dual Watchdog | Yes |
| Communication | |
| Ethernet Port | 10 / 100 Base TX (With Link, Activity LED Indicator) Automatic MDI/MDI-X Crossover |
| Digital Output | |
| Output Channels | 8 |
| Output Type | Source, Open Collector |
| Output Voltage | +10Vdc to 40Vdc |
| Max. Load Current | 650mA/channel at 25 °C |
| Overvoltage Protection | +48Vdc |
| Digital Input | |
| Input Channels | 8 |
| Input Type | Wet Contact (Sink, Source) |
| On Voltage Level | +10Vdc to 50Vdc |
| Off Voltage Level | +4Vdc Max. |
| Input Impedance | 10K Ohms |
| Counters | Max. Count: 4,294,967,285 (32 bits) |
| Max. Input Frequency : 500Hz | |
| Min. Pulse Width: 1 ms | |
| Overvoltage Protection | +70Vdc |
| 2 Way lsolation | |
| Ethernet | 1500 Vrms |
| I/O | 3750 Vrms |
| Mounting | |
| Din Rail Mount | Yes |
| Wall Mount | Yes |
| Power Requirements | |
| Protection | Power reverse polarity protection |
| Required Supply Voltage | +10Vdc to 30Vdc |
| LED Indicator | Yes |
| Power Consumption | 0.08A/24Vdc Max. |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Relative Humidity | 5 to 90% RH, non-condensing |
| Dimensions | |
| Dimensions ( W x H x D) | 123 mm x 72 mm x 35 mm |