tM-DA1P1R1
1-channel Analog Output, 1-channel Digital Input and 1-channel Relay Output Module
Features
The tM-DA1P1R1 is an RS-485 Interface module that offers 1 analog output channel, 1 digital input channel and 1 relay output channel. Analog output resolution is 12-bit with an output range of 0~10V and 0~20mA. The Digital input channel is dry contact type and provides a 16-bit counter function. The Relay output type is a Form C, and all I/O terminals provide 4 kV ESD protection and 3 kV intra-module isolation.
- Isolated Analog Output
- Isolated Digital Input
- Power Relay Output
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- 4 kV ESD Protection
- 3 kV Intra-module Isolation
- Wide Operating Temperature Range: -25 ~ +75°C
Applications
- Industrial Automation
- Industrial Machinery
- Building Automation
- Dimmer Control
- Food and Beverage Systems
- Semiconductor Fabrication
- Control Systems
Specifications
Analog Output | ||
Channels | 1 | |
Type | 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA | |
Resolution | 12-bit | |
Accuracy | +/-0.1% of FSR | |
DA Output Response Time | 10 ms | |
Voltage Output Capability | 20 mA | |
Current Load Resistance | 500 Ω | |
Digital Input/Counter | ||
Channel | 1 | |
Type | Dry | |
On Voltage Level | Close to GND | |
Off Voltage Level | Open | |
Counters | Channels | 1 |
Max. Count | 65535 (16-bit) | |
Max. Input Frequency | 100 Hz | |
Min. Pulse Width | 5 ms | |
Relay Output | ||
Channels | 1 | |
Type | Power Relay, Form C | |
Operating Load Voltage Range | 250 VAC or 30 VDC | |
Max. Load Current | NO : 10 A @ 250 VAC NC : 6 A @ 250 VAC |
|
Operating Time | 15 ms max. | |
Release Time | 5 ms max, | |
Mechanical Endurance | 1 X 107 OPS | |
Electrical Endurance | 5 X 104 OPS | |
Power On and Safe Value | Yes, Programmable |
Communication | ||
Interface | RS-485 | |
Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) | |
Baud Rate | 1200 ~ 115200 bps | |
Protocol | DCON, Modbus/RTU, Modbus/ASCII | |
Watchdog | Communication (Programmable) | |
LED Indicators | ||
Power | 1 LED as Power Indicator | |
Isolation | ||
Intra-module Isolation, Field-to-Logic | 2500 VDC | |
EMS Protection | ||
ESD (IEC 61000-4-2) | +/-4 kV Contact for Each Terminal | |
+/-8 kV Air for Random Point | ||
EFT (IEC 61000-4-4) | +/-4 kV for Power | |
Power Requirements | ||
Reverse Polarity Protection | Yes | |
Powered from Terminal Block | Yes, 10 ~ 30 VDC | |
Consumption | 1.8 W Max. | |
Mechanical | ||
Dimensions (W x L x H) | 52 mm x 98 mm x 27 mm | |
Installation | DIN-Rail Mounting | |
Environment | ||
Operating Temperature | -25°C ~ +75°C | |
Storage Temperature | -30 ~ +80°C | |
Humidity | 10 ~ 95% RH, Non-condensing |