PM-3114-100
Modbus RTU, 4 loops single-phase power meter (60 A), DIN Rail mount, supports input types: Vrms, Irms, kW, kWh, kVA, kVAh, kVAR, kVARh, PF,supports operating temperatures from -10 ~ +70°C (+14°F ~ +158°F).
Features
ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3000 series that gives you access to real-time electric usage for single-phase power measurement. With its high accuracy (<1%, PF=1 ), the PM-3000 series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters are equipped with revolutionary wired clip-on CT (various types, support input current up to 200 A). It operates over a wide input voltages range 10 ~ 300 VAC which allows worldwide compatibility. And with 2 channels relay outputs, it can be linked with sirens or lightings for alarm messages. It also supports Modbus RTU protocol for easy integration.
- True RMS Power Measurements
- Energy Analysis for 1P2W, 1P4W
- Current Measurements Up to 200 A with Different CT Ratio
- Voltage Measurements Up to 300 V
- Clip-on CT for Easy Installation
- W Accuracy Better than 1% (PF=1)
- Supports RS-485 Interface
- Supports Modbus RTU Protocol
- Supports 2 Power Relay Output (Form A)
Specifications
Model | PM-3114-100 | |
AC Power Measurement | ||
Wiring | 1P4W-4CT | |
Input Voltage | 10 ~ 300 V | |
Input Current | CT Φ10 mm (60 A); CTΦ16 mm (100 A); CTΦ24 mm (200 A) | |
Input Frequency | 50/60 Hz | |
W Accuracy | Better than 1% (PF=1) | |
Starting Current | >0.03A ( 60A ), >0.05A (100A ), >0.09A( 200A ) | |
Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF) | |
Data Update Rate | 1 Second | |
Communication | ||
RS-485 | Protocol | Modbus-RTU |
Baud rate | 9600, 19200 (default), 38400, 115200; DIP Switch Selectable | |
Data format | N, 8, 1 | |
Isolation | 2500 VDC | |
Ethernet | Protocol | - |
CAN Bus | Protocol | - |
Baud rate | - | |
Isolation | - | |
Alarm Output | ||
Power Relay | Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC | |
Power | ||
Input Range | +12 ~ 48 VDC | |
Power Consumption | 2 W | |
Mechanical | ||
Casing | Plastic (Flammability UL 94V-0) | |
Dimensions (W x L x H) | 127 mm x 105 mm x 33 mm | |
Module Installation | DIN-Rail Mounting | |
CT Installation | Clip-On | |
Environment | ||
Operating Temperature | -10 ~ +70 °C | |
Storage Temperature | -25 ~ +80 °C | |
Ambient Relative Humidity | 10% ~ 90% RH, Non-condensing |