I-97018/S
8-channel Thermocouple Input Module with CN-1824M Daughter Board. For use with WP-9000, XP-9000, LX-9000 and LP-9000 Series PAC Controllers. Supports Operating Temperatures -25°C ~ +75°C.
Features
The I-97018 is an 8-channel universal Analog Input module with an RS-485 interface. Designed for thermocouple measurement and features automatic cold-junction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. The innovative design of the enhanced model ensures that thermocouple measurement is more accurate than with the earlier design. Besides the thermocouple inputs, the I-97018 also supports voltage and current input. The voltage input range can be from +/-15 mV to +/-2.5 V. Up to 8 different types of Analog Input can be connected to a single module. Overvoltage protection of up to 240 Vrms is provided. The module also features per-channel open wire detection for the thermocouple and +4 ~ +20 mA input channels.
- 8-channel Analog Input
- Current, Voltage and Thermocouple Input
- Individual Channel Configuration
- Open Thermocouple Detection
- Temperature Output Consistency
- Stable Temperature Output in the Field
- 240 Vrms Overvoltage Protection
- 4 kV ESD Protection
- Dual Watchdog
- 3000 VDC Intra-module Isolation, Field-to-Logic
- Wide Operating Temperature Range: -25 to +75°C
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
Specifications
Communication
Interface
RS-485
Format
N, 8, 1
Baud Rate
1200 ~ 115200 bps
Protocol
DCON
Dual Watchdog
Yes, Module (1.6 Seconds), Communication (Programmable)
LED Display
System LED Indictor
1 LED as Power Indicator
I/O LED Indicator
-
Isolation
Intra-module Isolation, Field-to-Logic
3000 VDC
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
±8 kV Air for Random Point
Power
Power Consumption
0.6 W Max.
Mechanical
Dimensions (L x W x H)
144 mm x 30.3 mm x 134 mm
Environment
Operating Temperature
-25°C ~ +75°C
Storage Temperature
-40°C ~ +85°C
Humidity
10 ~ 90% RH, non-condensing
I/O Specifications
Analog Input
Channels
8
Wiring
Differential
Sensor Type
Thermocouple
J, K, T, E, R, S, B, N, C, L, M, LDIN43710
Voltage
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current
±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
Accuracy
±0.1% of FSR
Resolution
16-bit
Sampling Rate
10 Hz (Total)
Input Impedance
> 400 kΩ
Common Voltage Protection
±200 VDC
Individual Channel Configuration
Yes
Overvoltage Protection
240 Vrms
Open Wire Detection (for thermocouple only)
Yes
Temperature Output Consistency
Yes
Stable Temperature Output in the Field
Yes