ET-7219Z/S
Ethernet I/O Module with 2-port Ethernet Switch with 10-ch universal Analog Input, 3-ch Digital Output with DB-1820 Daughter Board. Support for both Modbus TCP and Modbus UDP Protocols. Thermocouple input. Current Input and voltage input capable. Built-in Web Server. Wide operating temperature range of -25°C ~ +75°C (-13°F ~ +167°F)
References & Support
Features
- Built-in Web Server
- Web HMI
- Support for both Modbus TCP and Modbus UDP Protocols
- Communication Security
- 2-port Ethernet Switch for Daisy-Chain Topology
- Dual Watchdog
- Wide Operating Temperature Range: -25°C ~ +75°C (-13°F ~ 167°F)
- I/O Pair Connection
- Built-in I/O
- AI: 10 Channels with 240 Vrms Overvoltage Protection
- DO: 6/3 Channels
The “Z” version is another milestone in the development of the thermocouple series and is a testament to the excellence of ICP DAS products. The ET-7219Z is specifically designed for extremely accurate thermocouple measurement and features automatic coldjunction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. Current input and voltage input are both supported. Another feature is that its ten input channels can be individually configured for different kinds of analog input. Open thermocouple detection and ESD/EFT/Surge protection mechanisms are also included. The six/five digital output channels can be set as alarm outputs with short-circuit protection and overload protection.
Specifications
Software | |
Built-In Web Server | Yes |
Web HMI | Yes |
I/O Pair Connection | Yes |
Communication | |
Ethernet Port | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
PoE | - |
Protocol | Modbus/TCP, Modbus/UDP |
Security | ID, Password and IP Filter |
Dual Watchdog | Yes, Module (0.8 second), Communication (Programmable) |
LED Indicators | |
L1 (System Running) | Yes |
L2 (Ethernet Link/Act) | Yes |
Digital Input /Digital Output Status | Yes |
PoE Power | - |
2 Way Isolation | |
Ethernet | - |
I/O | 2500 VDC |
EMS Protection | |
ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal and 8 kV Air for Random Point |
EFT (IEC 61000-4-4) | +/-4 kV for Power |
Power Requirements | |
Reverse Polarity Protection | Yes |
Powered from Terminal Block | 12 ~ 48 VDC |
Powered from PoE | Yes, IEEE 802.3af, Class1 |
Consumption | 3.6 W (Max.) |
Mechanical | |
Dimensions (W x L x H) | 76 mm x 120 mm x 38 mm |
Installation | DIN-Rail or Wall mounting |
Environmental | |
Operating Temperature | -25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature | -30 °C ~ +80 °C |
Humidity | 10 ~ 90% RH, non-condensing |
I/O Specifications
Analog Input | |||
Channels | 10 (Differential) | ||
Sensor Type | +/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) Thermocouple (J, K, T, E, R, S, B, N, C, L, M, and LDIN43710) |
||
Individual Channel Configuration | Yes | ||
Resolution | 16-bit | ||
Sampling Rate | 10 Samples/Second (Total) | ||
Accuracy | +/-0.1% of FSR or better | ||
Zero Drift | +/-0.5 μV/°C | ||
Span Drift | +/-25 ppm/°C | ||
Over Voltage Protection | 240 Vrms | ||
Input Impedance | >300 kΩ | ||
Common Mode Rejection | 86 dB Min. | ||
Normal Mode Rejection | 100 dB | ||
Temperature Output Consistency | Yes | ||
Stable Temperature Output in the Field | Yes | ||
Open Wire Detection | Yes | ||
Virtual Channel to Channel Isolation | +/-400 VDC | ||
Digital Output | |||
Channels | 3 | ||
Type | Isolated Open Collector | ||
Sink/Source (NPN/PNP) | Sink | ||
Max. Load Current | 700 mA/Channel | ||
Load Voltage | 5 VDC ~ 50 VDC | ||
Overvoltage Protection | 60 VDC | ||
Overload Protection | 1.4 A | ||
Short-circuit Protection | Yes | ||
Power-on Value | Yes, Programmable | ||
Safe Value | Yes, Programmable |
Thermocouple Type | Range°C |
J | -210 ~ +760 |
K | -270 ~ +1372 |
T | -270 ~ +400 |
E | -270 ~ +1000 |
R | 0 ~ +1768 |
S | 0 ~ +1768 |
B | 0 ~ +1820 |
N | -270 ~ 1300 |
C | 0 ~ 2320 |
L | -200 ~ +800 |
M | -200 ~ +100 |