XP-8138-CE6
1 I/O slot WinCE 6.0 Based Win-GRAF XPAC (OS: Multi-Language version) (RoHS)
Features
The Win-GRAF XPAC-8000-CE6 Series, XP-8138-CE6, is the new generation WinCE 6.0 based Win-GRAF XPAC-CE6 (Programmable Automation Controller) from ICP DAS. The XP-8138-CE6 is equipped with (1 GHz) dual-core running Windows CE 6.0 operating system, a variety of input/output ports (VGA, USB, Ethernet, RS-232/485), and a 1 I/O slot that can be used to integrate high performance parallel I/O modules (high profile I-8K Series) or serial I/O modules (high profile I-87K series)
The benefits of running Windows CE 6.0 on a XPAC device include hard real-time capability, achievable deterministic control and allowing PAC can have a PC-like window displays and operating environment. The PACs are capable of running Win-GRAF (IEC 61131-3 Standard) software to develop logic control applications, and also supporting M.S. VS 2008 software (VB .NET, C#) to develop HMI and data management applications that can exchange data with Win-GRAF applications.
- x86 CPU, 1.0 GHz, dual-core
- Windows CE 6.0
- Embedded Win-GRAF SoftLogic (IEC 61131-3)
- Hard Real-Time Capability
- VGA Port Output
- Modbus RTU/TCP (Master, Slave)
- Support eLogger HMI
- Redundant Power Inputs
- Support Dual PAC Redundant System
- Operating Temperature: -25 ~ +75 °C
Win-GRAF Workbench Feature
Win-GRAF is a powerful, PLC-like, softlogic development software. It is installed on PC with windows 7 or 8. It supports the international PLC language standard - IEC 61131-3 - Ladder Diagram (LD), Function Block Diagram (FBD), Sequential Function Chart (SFC), Structured Text (ST), Instruction Set (IL), suitable to develop applications for the full range of Win-GRAF PACs from ICP DAS.
- IEC 61131-3 Standard Open PLC Syntax (LD, FBD, SFC, ST, IL)
- Using ST Syntax in the FBD or LD Program
- Event Triggered Data Binding (Exchange Data between PACs)
- Online Debugging/Control/Monitoring, Offline Simulation
- On Line Change
- Various Protocols:
- Modbus TCP/UDP, Modbus RTU/ASCII Master
- Modbus TCP, RTU Slave
- DCON ...
- Plenty of Functions, Function Blocks, I/O Boards
- Redundancy (For XP-8x38-CE6 PAC only)
Specifications
System Software
OS
Windows CE 6.0
.Net Compact Framework
3.5
Embedded Service
FTP Server, ASP (Java Script, VB Script), SQL Compact Edition 3.5
SDK Provided
Dll for Visual Studio .NET 2005/2008
Multi-Language Support
English, German, French, Spanish, Russian, Italian, Japanese, Simplified Chinese, Traditional Chinese
Development Software
ISaGRAF Software
ISaGRAF Ver.3
IEC 61131-3 standard
Languages
LD, ST, FBD, SFC, IL & FC
Max. Code Size
2 MB
Scan Time
3 ~ 15 ms for normal program
15 ~ 50 ms (or more) for complex or large program
Non-Win-GRAF
Options: VS.NET 2008 (VB.NET, C#.NET, C)
CPU Module
CPU
x86 CPU, 1 GHz, dual-core
System Memory
2 GB DDR3
Non-volatile Memory, MRAM
512 KB (retain memory without battery support)
Flash
32 GB
EEPROM
16 KB
CF Card
8 GB (support up to 32 GB)
RTC (Real Time Clock)
Provide second, minute, hour, date, day of week, month, year
Programmable LED Indicator
2
64-bit Hardware Serial Number
Yes, for Software Copy Protection
Dual Watchdog Timers
Yes
Rotary Switch
Yes (0 ~ 9)
DIP Switch
Yes (8 bits)
Audio
Microphone-In and Earphone-Out
VGA & Communication Ports
VGA
Yes, (resolution: 1024 x 768, 800 x 600, 640 x 480)
Ethernet
RJ-45 x 2, 10/100/1000 Base-T (Auto-negotiating, Auto MDI/MDI-X, LED indicators)
USB 2.0
4
COM 1
Internal communication with the high profile I-87K series modules in slots
COM 2
RS-232 (RxD, TxD and GND); non-isolated
COM 3
RS-485
D2+, D2-; self-tuner ASIC inside
Isolation
3000 VDC
COM 4
RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232, Data+ and Data- for RS-485); non-isolated
COM 5
RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND); non-isolated
I/O Expansion Slots
Slot Number
1
Note: For High Profile I-8K and I-87K Modules Only
Mechanical
Dimensions (W x L x H), unit: mm
169 x 132 x 125 mm
Installation
DIN-Rail or Wall Mounting
Environmental
Operating Temperature
-25 ~ +75°C
Storage Temperature
-30 ~ +80°C
Ambient Relative Humidity
10 ~ 90% RH,non-condensing
Power
Input Range
+10 ~ +30 VDC
Isolation
1 kV
Redundant Power Inputs
Yes, with one power relay (1 A @ 24 VDC) for alarm
Capacity
3.7 A, 5 V supply to CPU and backplane, 1.3 A, 5 V supply to I/O expansion slots, 25 W in total
Consumption
16.6 W (0.69 A @ 24 VDC)
Win-DRAF Specifications
Protocols (Note that certain protocols require optional devices)
NET ID
1 ~ 255, for Modbus TCP/RTU Slave, user-assigned.
Modbus TCP Master
A max. of 200 IP links to access/control the devices supporting Standard Modbus TCP Slave protocol.
Modbus RTU/ASCII Master
A max. of 32 ports: COM2 ~ 33 style="color: red;">(*) to connect other Modbus Slave devices(Like M-7000). Recommend connecting no more than 32 devices in each port for better scan rate.
Modbus RTU Slave
A max. of 16 ports: COM2 ~ 33 (*) for connecting SCADA/HMI/OPC Server.
Modbus TCP Slave
Two Ethernet ports (LAN1 & LAN2) support up to 64 connections. If the PAC uses 1 connection to connect each PC/HMI, it can connect up to 64 PCs/HMIs; If the PAC uses 2 connections to connect each PC/HMI, it can connect up to 32 PCs/HMIs; If one of the Ethernet port malfunctions, the other one can still be used to connect the PC/HMI.
User-defined Protocol
Custom protocols can be applied at COM2 ~ 33 (*) by using Serial communication functions or function blocks.
DCON Remote I/O
A max. of 16 RS-485 ports: COM2 ~ 33 (*). Each port can connect max. 50 nos I-7000 series modules or 50 nos I-87xxxW I/O modules in expansion units (I-87K4, I-87K8, I-87K9, RU-87P8, RU-87P4). Recommend connecting no more than 32 modules in each port for better scan rate.
Local I/O Modules
Supports only high profile I/O modules. Slot 1 ~ 7 supports I-8xxxW parallel I/O modules and I-87xxxW serial I/O modules. (Refer Optional I/O List)
App Protection
Using the unique 64-bit (8 bytes) PAC serial number to generate a protection password by your own algorithm to protect your Win-GRAF application. Then, if someone intend to copy your application in the PAC to another new PAC with the same PAC model, this application will not work properly in that new PAC.
Redundancy
2 XP-8x38-CE6 can set a redundant system, when one is damaged or crashes, the other can still take up and continue the work. The system offers 3-line communication redundancy, LAN1, LAN2 and Alive Port (COM5), as long as one of the three communication lines still connects normally, this redundant system can normally control the process. The redundant system provides a public IP address that allows SCADA/ HMI software to access it without needing to determine which one is the Active IP.
Data Binding
Exchange data between ICP DAS Win-GRAF PAC via Ethernet ports (LAN1 and LAN2). The data transmission is event triggered. It is much efficient than polling way. Beside, user can setup the Redundant Binding in two ethernet ports by Software, then if one Ethernet port fail, it can switch to use the other port.
On Line Change
For application field that not allowed to stop the Win-GRAF program and wish to run a new program modified a little from the original program.
Modbus RTU I/O
When software enables Modbus RTU Master function, the PAC can connect ICP DAS M-7000 and tM series and LC series I/O modules which support Modbus RTU protocol.
Modbus TCP I/O
When software enable Modbus TCP Master function, the PAC can connect ICP DAS I-8KE4/8-MTCP, PETL-7000, tPET/tET series I/O modules which support Modbus TCP protocol.
HART Master
Support I-87H17W modules in slot 1 to 7 to communicate with other HART devices.
Schedule Control
Supports the "Schedule-Control Utility" (free) to implement schedule control. Each PAC can control max. 10 Targets (devices) with different schedule settings in each day / holiday / special day / season / year.
Retain Variables
Built-in the fast retain memory that can retain up to 12,000 Win-GRAF variables.
File Access and Data Log
The Win-GRAF supports file operation functions to read/write files in the PAC's micro_SD or flash memory to do data log or file access.
eLogger HMI
Support to run HMI program (developed by the eLogger) together with the Win-GRAF logic-control program in the same PAC.
Optional I/O List
Digital Input (DI)
I-8040W, I-8040PW, I-8046W, I-8051W, I-8052W, I-8053W, I-8053PW, I-87040W, I-87040PW, I-87046W, I-87051W, I-87052W, I-87053W, I-87053PW, I-87053W-A2, I-87053W-A5, I-87053W-E5
Digital Input/Output (DIO)
I-8042W, I-8050W, I-8054W, I-8055W, I-87042W, I-87054W, I-87055W
Digital Output (DO)
I-8037W, I-8041W, I-8041AW, I-8056W, I-8057W, I-87037W, I-87041W, I-87057W, I-87057PW
Digital Output (DO)
I-8037W, I-8041W, I-8041AW, I-8056W, I-8057W, I-87037W, I-87041W, I-87057W, I-87057PW
Relay Output
I-8060W, I-8063W, I-8064W, I-8068W, I-8069W, I-87061W, I-87061PW, I-87063W, I-87064W, I-87065W, I-87066W, I-87068W, I-87068W-2A, I-87069W, I-87069PW
AC Input
I-8058W, I-87053W-AC1, I-87058W, I-87059W
Analog Input (AI)
I-8017DW, I-8017HW, I-8017HCW, I-87017W, I-87017RW, I-87017RCW, I-87017DW, I-87017W-A5, I-87017ZW, I-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Analog Output (AO)
I-8024W, I-87024CW, I-87024UW, I-87024DW, I-87024RW, I-87024W, I-87028CW, I-87028UW, I-87028VW, I-87028VW-20V
Multifunction (DIO, AIO)
I-87026W
Temperature Input
Thermistor
I-87005W
RTD
-87013W, I-87015W, I-87015PW
T/C
I-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Strain Gauge
I-87016W
Counter/Frequency Input
I-8084W, I-87082W, I-87084W
Encoder Input
I-8093W
PWM Output
I-8088W
HART
I-87H17W
GPS
GPS-721
Communication Module
I-8112iW, I-8114W, I-8114iW, I-8142iW, I-8144iW
Temperature & Humidity Input
DL-100T485, DL-100T485-W, DL-100T485P, DL-100T485P-W (DCON Protocol) DL-100TM485, DL-100TM485-W, DL-100TM485P, DL-100TM485P-W (Modbus RTU Protocol)
* Note: COM6 ~ COM33 ports are located in the expansion boards (I-8142iW, I-8144iW, I-8112iW, I-8114W, I-8114iW) if they are installed in slot 1 ~ 7 of XP-8x38-CE6.
* ICP DAS recommends using NS-205/NS-208 or RS-405/408 (Ring Switch) Industrial Ethernet Switches.