WISE-7152
8-channel Isolated Source Type Open Collector Output and 8-channel Isolated Digital Input (32-bit Counter) Digital Output PoE Module. Can implement IF-Then Else type control logic. Communicable over Modbus TCP Protocol.
Features
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.
WISE-7152 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7152 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.
This module WISE-7152 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 8-channel isolated open collector outputs and 8-channel isolated wet contact digital inputs. Each output channel supports 650mA current driving +10 ~ 40 VDC and each digital input channel supports counter input.
- Built-in Web Server for IF-THEN-ELSE rule setting
- Built-in IF-THEN-ELSE rule enigne for logic operation
- No more programming. Just click and get done!
- Support IO, Counter, Timer, Email operations
- Modbus/TCP Protocol for SCADA Software Seamless Integration
- IEEE 802.3af-compliant Power over Ethernet (PoE)
- 10/100 Base-TX Ethernet
- 2-way Isolation/ESD Protection
- DO Type: 8 Isolation Open Collector (Sink Type)
- DI Type: 8 Isolation Wet Contact (Sink/Source)
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Specifications
Digital Input | ||
Input Channels | 8 | |
Input Type | Wet Contact (Sink, Source) | |
On Voltage Level | +10 VDC ~ +50 VDC | |
Off Voltage Level | +4 VDC Max | |
Input Impedance | 10 kΩ | |
Counters | Max. Count | 65535 (16 bits) |
Max. Input Frequency | 50 Hz | |
Min. Pulse Width | 10 ms | |
Overvoltage Protection | +70 VDC | |
Digital Output | ||
Output Channels | 8 | |
Output Type | Open Collector (Source) | |
Max Load Current | 650 mA/channel at 25 °C | |
Output Voltage | +10 VDC ~ +40 VDC | |
Overvoltage Protection | 47 VDC | |
Overload Protection | - | |
Short Circuit Protection | Yes | |
System | ||
CPU | 16-bit CPU | |
SRAM | 512 KB | |
Flash Memory | 512 KB | |
EEPROM | 16 KB | |
Watchdog | Yes | |
Communication | ||
PoE Ethernet Port | 10 / 100 Base-TX (With Link, Activity LED Indicator) and Automatic MDI/MDI-X | |
2 Way Isolation | ||
I/O | 3750 Vrms | |
EMS Protection | ||
ESD (IEC 61000-4-2) | 4 kV Contact for each terminal | |
EFT (IEC 61000-4-4) | +/-2 kV for Power | |
LED Indicators | ||
PoE | PoE On | |
L1 | System Running | |
L2 | Ethernet Link/Act | |
L3 | Ethernet 10/100M Speed | |
Power Requirements | ||
Reserve Polarity Protection | Yes | |
Powered from terminal block | Yes, 12 ~ 48 VDC | |
Powered from PoE | Yes, IEEE 802.3af, Class1 | |
Consumption | 4.3 W | |
Mechanical | ||
Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm | |
Installation | DIN-Rail or Wall mounting | |
Environment | ||
Operating Temperature | -25 ~ +75 °C | |
Storage Temperature | -30 ~ +80 °C | |
Humidity | 10 ~ 90% RH, non-condensing |
Software Specifications
Functions | |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Recipes | Set up THEN/ELSE action groups. |
8 P2P remote modules | Set up the connection information for the remote WISE modules. |
Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions | |
DI Channel | ON,OFF,ON to OFF,OFF to ON,Change |
Internal Register | =,>,<,>=,<=(value) |
DI Counter | =,>,<,>=,<=(value),Change |
DO Counter | |
Timer | Timeout,Not Timeout |
P2P | DI,AI,DI counter,DO counter,IR |
Rule Status | Enable,Disable |
THEN / ELSE Actions | |
DO Channel | ON,OFF,Pulse Output |
Internal Register | Change the value |
DI Counter | Reset |
DO Counter | |
Timer | Start,Stop |
Send | |
CGI Commands | |
Recipe | Execute |
P2P | DO(On/Off),AO,IR |
Rule Status | Enable,Disable |