User-defined I/O & Data Logger Module for Modbus TCP Devices, communicates over ethernet, RS-232 and RS-485, supports operating temperatures from -25 ~ +75°C

WISE-5800-MTCP

User-defined I/O & Data Logger Module for Modbus TCP Devices, communicates over ethernet, RS-232 and RS-485, supports operating temperatures from -25 ~ +75°C

  Price:  $699.00  

Features

WISE-5800-MTCP Application

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the labor and cost spent on system development.

WISE-5800-MTCP supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board. In addition, WISE-5800-MTCP also supports Modbus TCP slave devices. Based on the connection ability with Modbus TCP slave devices, WISE-5800-MTCP can provide user more flexibility in application field.

WISE-5800-MTCP supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It includes all advantages which WISE series controllers can provide. In addition, WISE-5800-MTCP provides data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. All setting can be completed through browser.

  • Built-in Web Server for IF-THEN-ELSE rule setting
  • Built-in IF-THEN-ELSE rule enigne for logic operation
  • No more programming. Click and get done!
  • Support I/O, Counter, Timer, Email, Recipe operations
  • Data logger and data files send back function supported
  • Modbus TCP/RTU Protocol for SCADA Software Seamless Integration
  • Support XW-Board
  • Support Modbus TCP Slave Devices(Up to 7)
  • SNTP Time Synchronization Supported

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment, etc.

Specifications

Support I/O Module List

I/O Type Functions Modules
XW-Board DI/DO XW107, XW110
DI/DO/AI/AO XW304, XW310, XW310C
Modbus TCP Slave Module Coil Output / Discrete Input / Input Register / Holding Register

Hardware Specifications

CPU Module
CPU 16-bit CPU
SRAM 768 KB
Flash 512 KB
EEPROM 16 KB
NVRAM 31 Bytes
microSD Expansion Support 1/2/4 GB microSD
RTC (Real Time Clock) Provide second, minute, hour, date of week, month and year
Watchdog Yes
Communication Ports
Ethernet RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X)
COM 1 RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max.
COM 2 RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed: 115200 bps max. (Reserved)
LED Indicators
System LED Yes (Red)
Ethernet Link LED Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received)
Hardware Expansion
I/O Expansion Bus Yes
Power Requirements
Protection Power Reverse Polarity Protection
Frame Ground Yes (for ESD Protection)
Input Range 12 ~ 48 VDC
Redundant Power Input Yes
Power Consumption 2.0 W
Mechanical
Dimensions (W x H x D) 91 mm x 123 mm x 52 mm
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Ambient Relative Humidity 10 ~ 90% RH (non-condensing)

Software Specifications

Functions
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions.
12 Schedules Setup prescheduled routine tasks.
12 Emails Send Email messages to pre-set Email receivers.
12 CGI Commands Send pre-set CGI commands.
12 Recipes Set up THEN/ELSE action groups.
Data Logger Set up the Data Logger configuration, include the data record format, and data file sending operation.
Modbus TCP/RTU Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions
DI Channel ON、OFF、ON to OFF、OFF to ON、Change
AI Channel =、>、<、>=、<=(value)
Internal Register
DI Counter =、>、<、>=、<=(value)、Change
Timer Timeout、Not Timeout
Schedule In Range、Out of Range
Rule Status Enable、Disable
THEN / ELSE Actions
DO Channel ON、OFF、Pulse Output ( apply to XW-Board only)
AO Channel Change the value
Internal Register
DI Counter Reset
Timer Start、Reset
Schedule Enable、Disable
Email Send
CGI Commands
Recipe Execute
Data Logger Start、Stop、One-Time Log
Rule Status Enable、Disable

Related Products