Copyright March 2002 by ICP DAS CO., LTD. All right reserved.

Trademark:
  Products, names and trade names appeared belongs to their respective owner. 

This document describe the way to set the Slave number of the 
I-7188XG controller.

1. Create a file folder named "7188XG" in your hard drive. 
   For example, "c:\7188XG".

2. Copy \Napdos\ISaGRAF\7188XG\Driver\7188xw.exe, 7188xw.ini
   from the CD_ROM into your "7188XG" folder.

3. Run "\7188XG\7188xw.exe" in your hard drive. A "7188xw" screen 
   will appear. 

4. Link from COM1 or COM2 of your PC to COM1 of the I-7188XG 
   controller by a RS232 cable. 

5. Power off the I-7188XG controller, connect pin "INIT*" to 
   "GND", and then power it up.

6. If the connection is Ok, messages will appear on the 
   7188xw screen.

      ICP_DAS MiniOS7 for I-7188xB Ver. 2.00 build 001,May 16 2003 17:27:38
      SRAM:512K, FLASH MEMORY:512K
      [CPU=RDC 8820-D]
      Serial number= 5A 5A 5A 5A 5A 5A 5A 5A
      i-7188XB>

7. Type "isa7188 *s=xxx" to set to a new Slave number.

      i-7188XB> isa7188 *s=5
      Set Slave number=5

8.Press ALT_X to exit "7188xw" and close the DOS SHELL, or 
   COM1/COM2 of the PC will be occupied. 

9. Remove the connection between "INIT*" - "GND", reset the 
    I-7188XG controller.

    