Download Now

Enter your information or login to view the document.


×
PROFIBUS Remote I/O Module with 12 Isolated Digital Inputs.

PROFI-5052

PROFIBUS Remote I/O Module with 12 Isolated Digital Inputs.

  Price:  $459.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

The PROFI-5052 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 12-channel isolated digital input with 5000Vrms field to logic isolation. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.

The PROFI-5052 is one of the PROFIBUS DP series products produced by ICP DAS. It provides the PROFIBUS DP communication protocol with any DP-Masters. The PROFI-5052 provides ±4KV ESD protection contacting for all terminals (include I/O Terminals and PROFIBUS connector). By applying the PROFI-5052, users can easily establish a PROFIBUS DP network with other DP-Masters. In advance, it can be used in the application of building automation, remote data acquisition, environment control and monitoring, laboratory equipment & research, factory automation, etc...

  • Support for PROFIBUS DP-V0 protocol
  • Detect transmission rate automatically(Max. 12Mbps)
  • Address 0~99 set by rotary switches
  • Network Isolation Protection
  • 3000VDC isolation protection on PROFIBUS side
  • 4KV ESD Protection (contact for any terminal)
  • Wide range of power input (DC 10~40VDC) and operating temperature (-25°C~+75°C)

PROFI-5052

Applications

  • Industrial Automation
  • Factory Automation
  • Process Automation
  • Etc…
Applications

Features

Protocol & Hierarchy
DP-V0 Slave
Supports Transmission Rate (kbps)
9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
Transmission Rate Setting
detected automatically
Address Setting
0~99 set by rotary switches
Indicators
PWR and RUN LEDs
I/O modules Configuration
Configured by GSD file
Network Isolation Protection
High Speed iCoupler
DC Isolation Protection
3000 VDC on PROFIBUS side
4KV ESD Protection
Contact for each terminal

 

Specifications

Hardware
ESD Protection
4 kV class A
PROFIBUS Interface
Controller
Profichip VPCLS2
Transceiver
ADI ADM2486
Connector
9-pin female D-Sub
Baud Rate (bps)
9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Transmission Distance (m)
Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
Isolation
3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol
DP-V0
LED
Round LED
PWR LED, RUN LED
Power
Power supply
Unregulated +10 ~ +40 VDC
Protection
Reverse polarity protection, Over-voltage brown-out protection
Power Consumption
1 W
I/O
Digital Input
12 Channels (Sink or Source), Isolated from each other.
Off Voltage Level: +1V Max. On Voltage Level: +4 ~ +30V
Input Impedance: 3KΩ in series with opto-coupler
Isolation Voltage: 5000Vrms
Mechanism
Installation
DIN-Rail
Dimensions
91 mm x 128 mm x 52 mm (W x L x H)
Environment
Operating Temp.
-25 ~ 75℃
Storage Temp.
-30 ~ 85℃
Humidity
5 ~ 95% RH, non-condensing

References and Support

Customer Reviews (0)

Be the first to leave a review.

Recently Viewed Items

×

Write a Review

Name


E-mail


Phone


Rating: out of 5 Stars
Review (max 1000 characters)

characters left