Download Now

Enter your information or login to view the document.


×
Ethernet/IP adapter to Modbus RTU Master and Modbus TCP Client Gateway, communicable over Modbus RTU, Modbus TCP, and EtherNet/IP protocols. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).

GW-7472

Ethernet/IP adapter to Modbus RTU Master and Modbus TCP Client Gateway, communicable over Modbus RTU, Modbus TCP, and EtherNet/IP protocols. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).

  Price:  $249.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

gw-7472 EtherNet/IP to Modbus RTU / Modbus TCP Gateway applicationThe GW-7472 EtherNet/IP adapter to Modbus RTU Master and Modbus TCP Client Gateway is helpful for data-exchanging between the Modbus RTU/Modbus TCP Network and the EtherNet/IP Network. It reads the register data from the Modbus RTU slaves as well as Modbus TCP servers and publishes these data to the input register data of the EtherNet/IP scanner. The output data transmitted by the EtherNet/IP scanner are updated to the register data of Modbus RTU slaves/Modbus TCP servers via the GW-7472. In order to save the installation space, the GW-7472 is offered in an amazing tiny size that makes it easy to install in anywhere, even directly attached to a serial device or embedded into a machine. The GW-7472 features a powerful 32-bit MCU to handle efficient network traffic and it provides the IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) with a standard category 5 Ethernet cable. Through the NS-205PSE, Poe switch, the GW-7472 can be powered via the Ethernet cable. When there is no PoE switch on site, the GW-7472 provide another way to be powered from DC adapters. These two power interfaces are redundant. If one fails, another will take it over to supply the proper power to the GW-7472.

General Features:

  • Powerful 32-bit MCU handles efficient network traffic
  • 10/100 Base-TX Ethernet, RJ-45 x1
  • Auto-negotiating, auto MDI/MDIX, LED Indicators
  • Redundant power inputs: PoE (IEEE 802.3af, Class 1) and DC jack
  • Automatic RS-485 direction control
  • Support ARP,TCP, UDP, ICMP, DHCP, BOOTP and TFTP protocols
  • Easy firmware update via Ethernet
  • Removable terminal block connector
  • Tiny form-factor and low power consumption
  • RoHS compliant with Halogen-free
  • Fire retardant materials (UL94-V0 Level)

EtherNet/IP Features:

  • Ethernet Protocol: EtherNet/IP adapter
  • Maximum number of connections for Explicit Messages: 6
  • Maximum number of connections for Implicit Messages: 1
  • Supported I/O connection methods:
    • Transport and trigger: Exclusive-Owner, Cyclic
    • Original to Target Type: POINT2POINT
    • Target to Original Type: POINT2POINT, MULTICAST
  • Device Configuration Option: EDS, Utility tool
  • Address Configuration: DHCP, Utility tool
  • EtherNet/IP Input/Output command data size: maximum 500 bytes
  • The numbers of the Modbus RTU slave and Modbus TCP servers input registers mapping to the input registers of the EtherNet/IP adapter of the GW-7472: maximum 500 bytes
  • The numbers of the Modbus RTU slave and Modbus TCP servers output registers mapping to the output registers of the EtherNet/IP adapter of the GW-7472: maximum 500 bytes

Modbus Features:

  • Modbus Protocol: Modbus RTU Master
  • Maximum support 30 Modbus RTU commands
  • Maximum support 10 Modbus TCP servers
  • Maximum support 8 Modbus commands for each one Modbus TCP server
  • Supported Modbus Function Codes:
    • 01 hex: Read Output Status
    • 02 hex: Read Input Status
    • 03 hex: Read Multiple Data Registers
    • 04 hex: Read Input Registers
    • 0F hex: Write Multiple Bits
    • 10 hex: Write Multiple Data Register
  • Maximum data size of one Modbus command: 240 bytes

Data Interchange Between Ethernet/IP and Modbus RTU

EtherNet/IP to Modbus RTU gateway

The GW-7472 is an EtherNet/IP Server with all the required EtherNet/IP objects. This section describes the EtherNet/IP Object Model and how to read/write the object data using EtherNet/IP Explicit and I/O messaging.


Utility

Ethernet/IP to Modbus gateway Utility Setting

We provide GW-7472 Utility tools for Windows 2K/XP/Vista and Windows 7, it includes:

  • Network parameters configuration
  • UART parameters configuration
  • Modbus RTU devices configuration
  • Auto search GW-7472 device
  • Easy test to transmit/receive EtherNet/IP data

Applications

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition
CE FCC RoHS WEEE

Specifications

Hardware
CPU
32-bit MCU
UART Interface
COM 1
2-wire RS-485
4-wire RS-422
COM 1 Connector
10-Pin Removable Terminal Block x 1
Protocol
Modbus RTU master and Modbus TCP client
Ethernet Interface
Ethernet
10/100 Base-TX, 8-pin RJ-45 x 1, (Auto-negotiating, Auto-MDI/MDIX, LED indicator)
PoE (IEEE 802.3af, Class 1)
Protocol
EtherNet/IP server
Power
Power supply
PoE: IEEE 802.3af, Class 1
DC jack: +12 ~ 48 VDC
Power Consumption
0.05 A @ 24 VDC
Mechanism
Dimensions
52mm X 95mm X 27mm(W x L x H)
Mounting
DIN-Rail
Flammability
Fire Retardant Materials (UL94-V0 Level)
Environment
Operating Temperature
-25 ~ 75 ℃
Storage Temperature
-30 ~ 80 ℃
Humidity
10 ~ 90% RH, non-condensing

References and Support

Customer Reviews (2)

July 7, 2016
Jesse
5/5

I use this with my Ethernet/IP PLC to get data from my 485 Modbus RTU flowmeter for my monitoring and control system. I set it up and was up and running in 15 minutes.


April 8, 2016
Stephen P.
5/5

works great with my AB PLC and handles traffic fast. would buy again in future applications.


Recently Viewed Items

×

Write a Review

Name


E-mail


Phone


Rating: out of 5 Stars
Review (max 1000 characters)

characters left