Download Now

Enter your information or login to view the document.


×
Modbus TCP Based Ethernet I/O Module with 2 Ethernet ports for daisy-chain networking, with 10/20-channel Analog Input (Current Input). Input Types are +/-150 mV, +/-500 mV, +/-1V, +/-5V, +/-10V, +/-20 mA ,0 ~ 20 mA, 4 ~ 20 mA(Jumper Selectable). Communicable over Modbus TCP and Modbus UDP, Supports operating temperatures of -25°C ~ +75°C (-13°F ~ 167°F) and has a din rail mount.

PET-7217-10

Modbus TCP Based Ethernet I/O Module with 2 Ethernet ports for daisy-chain networking, with 10/20-channel Analog Input (Current Input). Input Types are +/-150 mV, +/-500 mV, +/-1V, +/-5V, +/-10V, +/-20 mA ,0 ~ 20 mA, 4 ~ 20 mA(Jumper Selectable). Communicable over Modbus TCP and Modbus UDP, Supports operating temperatures of -25°C ~ +75°C (-13°F ~ 167°F) and has a din rail mount.

  Price:  $599.00  

Fastest Delivery: (Details) X Delivery Details
We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

PET-7217-10 Application Image

The PET-7217-10 is a module with 10-channel differential or 20-channel single-ended analog inputs. It provides programmable input range on all analog channels (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA and 4 ~ 20 mA). Each analog channel is allowed to configure an individual range and has 240 Vrms high overvoltage protection. Each analog input can be programmed to accept voltage or current as input depending upon the position of corresponding jumper. The sampling rate of PET-7217-10 has two modes; fast mode and normal mode for your consideration. PET-7217-10 also has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation.

  • Built-in Web Server
  • Web HMI
  • Support for both Modbus TCP and Modbus UDP Protocols
  • Communication Security
  • 2-port Ethernet Switch for Daisy-Chain Topology
  • Dual Watchdog
  • Wide Operating Temperature Range: -25 ~ +75°C
  • I/O Pair Connection
  • Built-in I/O
    • AI: 10/20 Channels with 240 Vrms Overvoltage Protection

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.

Daisy-Chain Ethernet Cabling

The ET-7200/PET-7200 Series has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.

application2

LAN Bypass

LAN Bypass feature guarantees the Ethernet communication. It will automatically active to continue the network traffic when the ET-7200/PET-7200 looses its power.

application3

Communication Security

Account and password are needed when logging into the web server. An IP address filter is also included, which can be used to allow or deny connections with specific IP addresses.

Support for both Modbus TCP and Modbus UDP Protocols

The Modbus TCP, Modbus UDP slave function on the Ethernet port can be used to provide data to remote SCADA software.

Built-in I/O

Various I/O components are mixed with multiple channels in a single I/O module, which provides the most cost effective I/O usage and enhances performance of the I/O operations.

Dual Watchdog

The Dual Watchdog is consists of a Module Watchdog and a Communication Watchdog. The action of AO,DO are also associated to the Dual Watchdog.
Module Watchdog is a built-in hardware circuit to monitor the operation of the module and will reset the CPU if a failure occurs in the hardware or the software. Then the Power-on Value of AO,DO will be loaded.
Communication Watchdog is a software function to monitor the communication between the host and the I/O module. The timeout of the communication Watchdog is proprgrammable, when the I/O doesn't receive commands from the host for a while, the watchdog forces the AO,DO to pre-programmed Safe Value to prevent unpredicatable damage of the connected devices.

Highly Reliable Under Harsh Environment

  • Wide Operating Temperature Range: -25 ~ +75°C
  • torage Temperature: -30 ~ +80°C
  • Humidity 10 ~ 90% RH (Non-condensing)

I/O Pair Connection

This function is used to create a AI/DI to AO/DO pair through the Ethernet. Once the configuration is completed, the I/O module can poll the status of remote AI/DI devices and then use the Modbus TCP protocol to continuously write to a local AO/DO channels in the background.

application4 application5

Power-on Value and Safe Value

Besides setting by the set AO,DO commands, the AO,DO can be set under two other conditions.
Power-on Value: The Power-on Value is loaded into the AO,DO under 3 conditions: Power-on, reset by Module Watchdog, reset by reset command.
Safe Value: When the Communication Watchdog is enabled and a Communication Watchdog timeout occurs, the “safe value” is loaded into the AO,DO.

application6

Specifications

Software
Built-In Web Server Yes
Web HMI Yes
I/O Pair Connection Yes
Communication
Ethernet Port 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE Yes
Protocol Modbus TCP, Modbus UDP
Security ID, Password and IP Filter
Dual Watchdog Yes, Module (0.8 seconds), Communication (Programmable)
LED Indicators
for System Running Yes
for Ethernet Link/Act Yes
for DI/DO status -
PoE Power Yes
2 Way Isolation
Ethernet -
I/O 2500 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±2 kV for Power Line
Surge (IEC 61000-4-5) ±2 kV for Power Line
Power
Reverse Polarity Protection Yes
Powered from Terminal Block 12 ~ 48 VDC
Powered from PoE -
Consumption 3.8 W
Mechanical
Dimensions (W x L x H) 76 mm x 120 mm x 38 mm
Installation DIN-Rail or Wall mounting
Environmental
Operating Temperature -25°C ~ +75°C (-13°F ~ +167°F)
Storage Temperature -30°C ~ +80°C (-22°F ~ +176°F)
Humidity 10 ~ 90% RH, non-condensing

I/O Specifications

Analog Input
Channels 10 differential or 20 single-ended (Note1),
software selectable
Type +/-150 mV, +/-500 mV, +/-1V, +/-5V, +/-10V
+/-20 mA ,0 ~ 20 mA, 4 ~ 20 mA
(Jumper Selectable)
Individual Channel Configuration Yes
Resolution 16-bit
Sampling Rate Normal Mode 10 Samples/Second (Total)
Fast Mode 50 Samples/Second (Total)
Accuracy Normal Mode +/-0.1%
Fast Mode +/-0.5% or better
Zero Drift +/-0.5 μV/°C
Span Drift +/-20 μV/°C
Overvoltage Protection Differential 240 Vrms
Single-ended 150 Vrms
Common Voltage Protection ±200 VDC
Overcurrent Protection Yes, 50 mA at 110 VDC
Virtual Channel to Channel Isolation Yes, 400 VDC
Open Wire Detection for 4 ~ 20 mA Yes
Input Impedance Voltage 2 MΩ (Differential), 1 MΩ (Single-ended)
Current 125 Ω
Common Mode Rejection 86 dB Min.
Normal Mode Rejection 100 dB
Note1: Differential mode can be used for voltage input and current input. Single-Ended mode can be used for voltage input only.

References and Support

Customer Reviews (0)

Be the first to leave a review.

Recently Viewed Items

×

Write a Review

Name


E-mail


Phone


Rating: out of 5 Stars
Review (max 1000 characters)

characters left