M-7080B
2-channel Counter/Frequency Input with battery backup. Communicates over Modbus RTU and DCON protocol. Comes with free EZ Data Logger software for data logging and remote monitoring. Supports operating temperatures between -25°C ~ 75°C (-13°F ~ +167°F). Has a din rail mount.
Features
The M -7080B is intelligently designed to provide signal conditioning, system monitoring, and safe value settings. It is a Counter/Frequency Input Module with Battery Back Up that supports modbus RTU. In case of power failure, it will keep the readings due to battery backup. It is a cost-effective solution for a wide range of valuable industrial control signals and systems.
The DCON utility can help users to configure and test the M-7080 High Speed Counter / Frequency Input module. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. The communication interface is modbus protocol via RS-485 and also Modbus RTU to easily communicate with most popular SCADA/ HMI software and PLCs. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
- 2-channel counter/frequency digital input, wet contact, sink type
- Equipped with battery backup, can work in case of power loss.
- Supports Modbus RTU and DCON protocols
- ±4 kV Contact ESD protection for each Terminal
- Supports power input range of 24 ~ 30 VDC
- Power consumption: 2.0 W
- DIN-Rail or Wall Mounting
- Supports operating temperatures of -25 ~ +75°C (-13F ~ 167F).
Specifications
Counter Input | |
Channels | 2 independent 32-bit counters, counter 0&1 |
Input Type | Isolated or non-isolated |
Isolated Input Level | Logic level 0:+1V max. |
Logic level 1: +3.5 to 30V | |
Isolation Voltage | 3750Vrms |
Non-Isolated Input Level (Programmable) | Logic level 0: 0 to +5V (default= 0.8V) |
Logic level 1: 0 to +5V (default= 2.4V) | |
Maximum Count | 32bit (4,294,967,295) |
Programmable Digital Noise Filter | 2us to 65ms |
Alarming | alarm on counter 0 or counter 0 & 1, programmable |
Counter Rreset Value | programmable |
Built-in Virtual Battery Back Up | for Counter Value |
Frequency Measurement | |
Input Frequency | 1Hz to 100KHz max. |
Gate Time | 1.0 or 0.1sec, programmable |
Digital Output | |
Channels |
2 |
Output Type | Source, Open-Collector |
Output Voltage | 30V max. |
Output Current | 30mA max |
Interface | |
Interface | RS-485 |
Format | N, 8, 1 |
Baud Rate | 1200 ~ 115200bps |
LED Display | |
1 LED | as Power/ Communication indicator |
Power | |
Input Voltage Range | 24~30VDC |
Power Consumption | 2.0W |
Protocol | |
Support Modbus and DCON Protocol | Yes |
Environment | |
Operating Temperature | -25 to 75°C |
Storage Temperature | -40 to 85°C |
Humidity | 5 to 95%, non-condensing |