M-7017mC-16
16 Channel Current Input Module and Data Logger. Stores up to 100,000 Records. Communicable over Modbus RTU.
Features
The M-7017mC-16 is equipped with 16-channel current inputs, designed to measure current. Its user-friendly design saves both time and effort when measuring current with its built-in resistors, allowing to measure current directly without needing to add an external resistor. The module also provides 4 kV ESD protection and 110 VDC overvoltage protection for the current input, and features 3000 VDC intra-module isolation and open wire detection for 4 ~ 20 mA input. The sampling rate on the M-7017mC-16 is adjustable, allowing either fast mode or normal mode. The M-7017mC-16 comes with a data logger to record current input from all 16 channels, including date and time stamps, and stores up to 100,000 downloadable records
- 16-channel Current Input
- Jumper Selectable Differential or Single-ended Wiring
- 16-bit Resolution
- Adjustable Sampling Rate
- Storage for up to 100,000 Records from16-channel Current Input
- Built-in Resistor to Simplify Current Measurement
- 110 VDC Overvoltage Protection
- 4 kV ESD and EFT Protecton
- 2 kV Surge Protection
- Dual Watchdog
- 3000 VDC Intra-module Isolation
- Wide Operating Temperature Range: -25 to +75°C
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
Specifications
Communication
Interface
RS-485
Bias Resistor
Yes, 1kΩ bias resistor by Jumper selectable
Format
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate
1200 to 115200 bps
Protocol
Modbus RTU, DCON
Dual Watchdog
Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator
Yes, 1 as Power/Communication Indicator
I/O LED Indicator
-
7-Segment LED Display
-
Isolation
Intra-Module Isolation, Field-to-Logic
3000 VDC
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
EFT (IEC 61000-4-4)
±4 kV to Power
Surge (IEC 61000-4-5)
±2 kV for Power Line
Power
Reverse Polarity Protection
Yes
Input Range
+10 ~ +48 VDC
Consumption
0.6 W
Mechanical
Dimensions (L x W x H)
120 mm x 76 mm x 42 mm
Installation
DIN-Rail or Wall Mounting
Environment
Operating Temperature
-25 to +75°C
Storage Temperature
-40 to +85°C
Humidity
10 to 95% RH, Non-condensing
I/O Specifications
Analog Input
Channels
16
Wiring
Differential or Single-ended Wiring (Jumper Selectable)
Types
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA
Resolution
16-bit
Sampling Rate
Normal Mode
10 Hz total
Fast Mode
200 Hz total
Accuracy
Normal Mode
+/-0.1%
Fast Mode
+/-0.5%
Zero Drift
+/-20 uV/°C
Span Drift
+/-25 ppm/°C
Common Voltage Protection
25 VDC
Individual Channel Configuration
Yes
Overvoltage Protection
110 VDC
Overcurrent Protection
Yes, 50 mA at 110 VDC
Virtual Channel to Channel Isolation
-
Open Wire Detection for 4 ~ 20 mA
Yes
Real Time Clock
Yes
Data Logger
Yes, up to 100,000 records from 16 current input channels