I-2532
CAN to Fiber Converter with ST Connector. Supports operating temperatures from -25°C to 75°C
References & Support
Features
Fiber optic transmission medium is a good material to protect data transmission from EMI/RFI interference. It has been used in harsh environments extensively. CAN bus is famous in industrial applications. In order to solve the problem between using different transmission mediums, I-2532 is specially designed for converting the electrical CAN bus signal to fiber optic cables.
The fiber length between two I-2532s can be up to 1.4km (4593ft). It is mainly decided by the cable attenuation of fiber and the CAN bus baud. I-2532 is the economical solution for applications which require protecting the data transmission from electrical exposure, surges, lightning or chemical corrosion.
- Compatible with CAN specifications 2.0A and 2.0B
- Fully compatible with the ISO 11898-2 standards
- Supports baud rates up to 500 Kbps
- Jumper for 120Ω terminator resistor of CAN bus
- Fiber Port: ST (Multi-mode)
- Wave Length: 850 nm
- Auto-baud detection
- up to 100 nodes on CAN port
- Removable terminal block
- Mount easily on DIN-rail
- Applications
- Control System
- Building Automation
- Factory Automation
- Distributed data acquisition
Specifications
I-2532 |
|
CAN Port Channels | 2 |
CAN Connector | 8-pin removable screw terminal × 1 |
Fiber Connector | ST (Multi-mode) Fiber Port × 2 |
Wave Length | 850 nm |
Fiber Cable | 62.5/125 μm |
Baud Rate | 10K ~ 500Kbps |
Terminator Resistor | Selectable 120Ω terminator resistor by jumper |
Support Protocol | CAN 2.0A/2.0B |
Propagation Delay | 125ns max (125ns delay shortens bus line length by ~25m) |
Power Requirement | Unregulated +10VDC ~ +30 VDC Power reverse protection,Over-Voltage brown-out protection |
Power Consumption | 0.5W max |
LED | Power LED × 1, Transmit LED × 1, Receive LED × 1 |
Operating Temp. | -25°C to 75°C |
Storage Temp. | -40°C to 80°C |
Humidity | 5~95% non-condensing |
Dimensions | 32.30mm × 99.00mm × 77.50mm (H x W x D) |