8-channel Current Input, Voltage Input, Analog Input with High Voltage Protection and 4-channel Isolated Digital Output Data Acquisition Module, communicable over Ethernet and Modbus TCP Protocol. Supports operating temperatures between -25 to 75°C.
Features
***This Product Has Been Phased Out and Replaced by ET-7019Z***
The ET-7019, a web-based Ethernet I/O module, features a built-in web server, which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Besides, with the web HMI function, no more programming or HTML skills are needed; creating dynamic and attractive web pages for I/O monitoring and I/O control would be fun to engineers ever after. The ET-7019 offers easy and safe access for users from anytime and anywhere! In addition, ET-7019 also supports Modbus/TCP protocol that makes seamless integration to SCADA software.
The ET-7019 is a 16-bit, 8-channel differential analog inputs and 4-channel digital ouputs module that provides programmable input range on all analog channels(±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA and thermpocouples) and digital output can be set alarm output. Each analog channel is allowed to configure an individual range and has 240 Vrms high over voltage protection.
Specifications
CPU | |
CPU | 80186 CPU (80MHz) |
SRAM | 512K Bytes |
Flash Memory | 512K Bytes |
EEPROM | 16K Bytes |
Dual Watchdog | Yes |
Communication | |
Ethernet Port | 10 / 100 Base-TX (With Link, Activity LED Indicator) Automatic MDI/MDI-X Crossover |
Analog Input | |
Input Channels | 8 Differential |
Input Type | ±15 mV, ±50 mV, ±100 mV, ±50 mV, ±500 mV, ±1 V, ±5 V, ±10 V Thermocouple (J, K, T, E, R, S, B, N, C, L, M, LDIN43710) ±20mA, 0~20mA, 4~20mA (jumper selectable) |
Resolution | 16-bit |
Sampling Rate | 10 samples/Sec. total |
Accuracy | ±0.1 % or better |
BandWidth | 15.7 Hz |
Zero drift | ±20 μV/°C |
Span drift | ±25 ppm/°C |
Input Impedance | Voltage: >1 M Ohms, Current: 125 Ohms |
Common Mode Rejection | 86 dB min. |
Normal Mode Rejection | 100 dB |
Open Thermocouple Detection | Yes |
Individual Channel Configuration | Yes |
Over Voltage Protection | 240 Vrms |
ESD Protection | 4 kV Contact for each terminal, and 8KV Air for random point |
EFT Protection | 4 kV for Power |
Digital Output | |
Output Channels | 4 (Sink) |
Output Type | Isolated Open Collector |
Max Load Current | 700 mA/ Channel |
Load Voltage | 5 VDC ~ 50 VDC |
2 Way Isolation | |
Ethernet | 1500 VDC |
AI and DO | 2500 VDC |
Mounting | |
Din Rail Mount | Yes |
Wall Mount | Yes |
LED Display | |
L1 LED | as Run indicator |
L2 LED | as Link/Act indicator |
L3 LED | as 10/100 M indicator |
Power Requirements | |
Protection | Power reverse polarity protection |
Required Supply Voltage | +10 VDC ~ 30 VDC (non-regulated) |
Power consumption | 0.10 A/24 VDC |
Environment | |
Operating Temperature | -25 °C ~ +75 °C |
Storage Temperature | -30 °C ~ +80 °C |
Relative Humidity | 5 to 90% RH, non-condensing |
Dimensions | |
Dimensions(W x L x H ) | 123 mm x 72 mm x 35 mm |