We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

  • Built-in Web Server
  • Support Modbus TCP/UDP Protocols
  • 2-port Ethernet Switch (LAN Bypass) for Daisy-Chain Wiring
  • Dual Watchdog
  • I/O Pair Connection (Push and Pulling)
  • Built-in I/O
    • ET-2261: 10-channel Relay Output
    • ET-2261-16: 16-channel Relay Output
  • LED Display to Indicate the I/O status
  • Wide Operating Temperature Range: -25 ~ +75 °C

Introduction

Providing various digital I/O functions, the ET-2261/2261-16 module is an Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2261/2261-16 module perfect integration with the HMI, SCADA, PLC and other software systems.

The ET-2261 supports 10 Form A electromechanical Relays Output channels, while the ET-2261-16 supports 16 Form A electromechanical Relays Output channels. With 2 Ethernet ports, the ET-2261/2261-16 allows daisy chain connection which permits the flexibility in locating devices, eases installation and lowers infrastructure costs. It features 8 kV ESD protection, 4 kV EFT protection, 3 kV surge and 3000 VDC I/O isolation to enhance noise protection capabilities in industrial environments.

The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2261 module can poll the status of remote DI channels via the Modbus TCP protocol and write data to local DO channels.

It is equipped with removable terminal block connector for easy and robust wiring in industrial situations, and features a powerful 32-bit ARM MCU to handle efficient network trafficking.

CE FCC RoHS WEEE

Specifications

Software
Built-in Web Server Yes
CPU Module
CPU 32-bit ARM
Watchdog Timer Yes, Module, Communication (Programmable)
Isolation
2-way Isolation Ethernet: 1500 VDC
I/O: 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±8 kV Contact for Each Terminal and
±16 kV Air for Random Point
Surge (IEC 61000-4-5) ±3 kV for Power Line
LED Indicators
Status Run, Ethernet, I/O
Relay Output
Channels 16
Type Power Relay, Form A (SPST N.O.)
Contact Rating 5 A @ 250 VAC/24 VDC (Resistive Load)
Operate Time 10 ms (max.)
Release Time 5 ms (max.)
Electrical Endurance 10^5 ops
Mechanical Endurance 2 x 10^7 ops
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-Tx, Switch Ports
LAN bypass Yes
Security Password and IP Filter
Protocol Modbus TCP, Modbus UDP, and MQTT
Power
Reverse Polarity Protection Yes
Consumption 4.71 W (max.)
Powered from Terminal Block +10 to +48 VDC
Mechanical
Casing Plastic
Dimensions (mm) 31 x 157 x 126 (W x L x H)
Installation DIN-Rail
Environmental
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing