CL-213-E
Remote PM2.5/CO/CO2/Temperature/Humidity/Dew Point Data Logger Module
Features
- Able to record PM2.5, CO, CO2, Temperature, Humidity and Dew Point Measurements
- Non-dispersive Infrared (NDIR) CO2 Sensor
- Up to 450,000 records with date and time stamps
- Supports the DCON, Modbus RTU/TCP, and MQTT Protocols
- Includes RS-485/Ethernet Communication Interfaces
- Relay Output for Alarm or IAQ Device Control
Introduction
The CL-200 series of data logger devices can be used to record PM2.5, CO, CO2, temperature, humidity and dew point information, including the date and time stamps, and are able to store up to 450,000 downloadable records. Real-time data can be accessed from the CL-200 data logger from anywhere and at any time using the free Windows software, the iOS App, or the Android App, as long as they are connected to the same local network as the data logger. Support is provided for common industrial protocols such as DCON, Modbus RTU, and Modbus TCP, as well as the emerging machine-to-machine (M2M)/)IoT (Internet of Things) connectivity protocol – MQTT. The CL-200 data logger can be connected via widely used communication interfaces including RS-485, Ethernet and PoE, meaning that the device can be easily integrated into existing HMI or SCADA systems, ensuring trouble-free maintenance in distributed control systems.
|
|||
Simple and Powerful DL-300 Utility
The DL-300 Utility is a powerful tool that is designed for confi guring the modules, monitoring real-time data, grouping DL-300 and CL-200 modules to view and manage the status of distribution groups, downloading log data, which can be exported to a CSV file that can then be imported into any industry-standard software or spreadsheet for analysis.
|
![]() |
Applications
|
||||
Indoor or Underground Parking Lot Automatic Monitoring Solution The air quality automation system for indoor or underground parking lot can use the CL-200 series modules to monitor the health and safity information, such as PM2.5, CO, CO2, temperature, humidity, dew point, and more... |
||||
![]() |
Specifications
System Specifications
Model | CL-210-E | CL-211-E | CL-212-E | CL-213-E | |
System | |||||
PM2.5/CO/CO2/RH/T Alarm | Yes | ||||
Real Time Clock | Yes | ||||
Data Logger | Yes, up to 450,000 records | ||||
Relay Output | Form A×1, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
||||
Interface | RS-485/Ethernet | ||||
Electrical | |||||
Powered from Terminal Block | +12 to +48 VDC | ||||
Power Consumption | Non-PoE | 2.5 W (Max.) | 2.66 W (Max.) | 2.9 W (Max.) | 3.24 W (Max.) |
PoE | 2.65 W (Max.) | 2.73 W (Max.) | 3.22 W (Max.) | 3.41 W (Max.) | |
Mechanical | |||||
Installation | Ceiling Mounting/Wall Mounting | ||||
Protection Class | IP20 | ||||
Dimensions (D x H) | Ø 150 mm x 53 mm | ||||
Environment | |||||
Operating Temperature | 0 to +50°C | ||||
Storage Temperature | -30 to +75°C | ||||
Humidity | 10 to 90% RH, Non-condensing |
I/O Specifications
Model | CL-210-E | CL-211-E | CL-212-E | CL-213-E |
PM2.5 Measurement | ||||
Range | 0 ~ 400 μg/m3 | |||
Resolution | 1μg/m3 | |||
Response Time | <= 1 min. | |||
CO Measurement | ||||
Range | - | 0 to 1000 ppm (Electrochemical) | - | 0 to 1000 ppm (Electrochemical) |
Resolution | - | 1 ppm | - | 1 ppm |
Accuracy | - | ±5% of measured value | - | ±5% of measured value |
Response Time | - | 30 seconds | - | 30 seconds |
Warm-up Time | - | 60 seconds | - | 60 seconds |
CO2 Measurement | ||||
Range | - | 0 to 9999 ppm (NDIR) | ||
Resolution | - | 1 ppm | ||
Accuracy | - | ±40 ppm ±3% of measured value | ||
Response Time | - | 120 seconds | ||
Warm-up Time | - | 5 minutes | ||
Temperature Measurement | ||||
Range | -10 to +50°C | |||
Resolution | 0.1°C | |||
Accuracy | ±0.6°C | |||
Relative Humidity Measurement | ||||
Range | 0 to 100% RH, Non-condensing | |||
Resolution | 0.1% RH, Non-condensing | |||
Accuracy | ±5% RH, Non-condensing | |||
Dew Point | ||||
Range | Calculated using temperature and relative humidity | |||
Resolution | 0.1°C |