WISE Active IO Function


Active I/O Introduction

WISE-580x equips the “Active I/O sending” function. There are two parts in this function: “I/O Data Table Configuration” and “Active sending of I/O Data Table”. Even though WISE-580x allows to connect with up to 16 I-7000 I/O modules, and 4 Modbus RTU Slave I/O modules at the same time, however, the channel data of each I/O module that WISE-580x received is located in the different Modbus Address memory block of WISE-580x. Therefore, when using SCADA software to retrieve the data, the SCADA software must poll each I/O module’s channel data separately. It is impossible to poll all WISE-580x I/O module’s channels data at one time. In order to improve the efficient of the data communication between WISE-580x and SCADA software, WISE-580x provides “I/O Data Table Configuration” function. It allows to rearrange the I/O channels data from different I/O modules and puts them into a continuous Modbus address memory block, and then SCADA software can retrieve all I/O channels data from different modules by using one single Modbus command. Comparing to traditional polling mechanism, it will greatly save time and polling attempts. In addition to the “I/O Data Table Configuration” function, WISE-580x also provide the “Active sending of I/O Data Table” function. It allows WISE-580x to actively send the content of I/O Data Table to SCADA software through Modbus TCP protocol without polling mechanism from SCADA software.

Please note: The SCADA software must equip the Modbus TCP Slave function to receive the content of I/O Data Table that sent by WISE-580x.

 

Active I/O Introduction

The configuration page is shown as below:

 

Follow the following steps:

  1. Select “Enable I/O Data Table configuration” to enable the I/O Data Table function, then the I/O Data Table and the configuration UI will be shown as follow:


  2. There are two data arrangement types for the I/O Data Table: ”Coil and Register” and “Register (Merge Coil into Register)”. In the ”Coil and Register” type, The I/O module’s DI/DO/Modbus Coil data will be saved in the Coil area of the I/O Data Table, and the I/O module’s AI/AO/Modbus Register/Internal Register data will be saved in the Register area of the I/O Data Table. If you select the “Register (Merge Coil into Register)” type, then the I/O module’s DI/DO/Modbus Coil data will be saved in the Register area of the I/O Data Table in binary format. Each Register can store 16 Coils data.
  3. The “Module” field allows to select specific I/O module or Internal Register that will be used in the I/O Data Table; select the “Channel” and “Index” number from the drop down lists to edit the table configuration of the I/O module’s channel.


    When you complete the setting of Module, Channel and Index, please click the “Add” button to add the channel of the I/O module into the I/O Data Table. You can use the Control Panel in the right-bottom of the I/O Data Table to “Move” or “Delete” the channel setting of the I/O Data Table. The “Clear All” button is used to clear all channel settings in the I/O Data Table. “Trim” button is used to remove all the excess space between the channel settings to make all channel settings of the I/O Data Table to be more compact.

    In the I/O Data Table, the “Local Address” in the left side is the address for saving I/O Data Table in the WISE Modbus Address Table. The starting address is 1230(Base 0 & Decimal format). The maximum length is 300. Therefore, SCADA software can connect to the WISE Modbus address 01230 to inquire the first Coil data in the I/O Data Table, and connect to the WISE Modbus address 41230 to inquire the first Register data in the I/O Data Table. If the “Active sending of I/O Data Table” function is enabled, the “Receiver Start Address” in the upper area of the I/O Data Table is the address of the Receiver’s(SCADA software) Modbus starting address. The content of the I/O Data Table that WISE-580x send actively to Receiver’s(SCADA software with Modbus TCP Slave function) will be saved from the starting address. The naming rule of the channel inside the I/O Data Table is: (RS-485 Address) Channel Type + Channel Index. For example, (1)DI0 is for the DI0 channel of the I/O module with RS-485 address 1.

    The following figure shows an example of the data arrangement of the I/O Data Table for the “Register (Merge Coil into Register)” type.


  4. Enable the “Active sending of I/O Data Table”, then WISE-580x will actively send all the I/O Data Table‘s channels data to the SCADA software.


    It is required to set the Receiver’s (SCADA software) IP address, the Modbus TCP Slave’s Port number and NetID of the Receiver’s, the Timeout value, and the type of “Timing to send out I/O Data”. There are two options for the “Timing to send out I/O Data”, one option is to send out the data when an I/O channel value change takes place, the other is to send out the data at periodic time schedule.

Active I/O Application Example

Scenario Example Document

WISE-580x provides “Active I/O” function. Based on this function, WISE-580x can actively send (push) the channels value of the I/O modules that connected to WISE-580x to SCADA software (or HMI device) by event trigger (I/O channel value changed) or periodic cycle. This function greatly enhances the data communication efficiency  between WISE-580x and SCADA software (or HMI device) via traditional polling mechanism. The following scenario assume using WISE-5801 controller in a greenhouse environment monitoring system. It is required to monitor the temperature and device’s status of various greenhouses at the same time. By the traditional polling mechanism, the control center must poll all controllers one by one to get the temperature and device’s status of each greenhouse. Now with this function, the WISE-580x controller in each greenhouse will actively send back the temperature value and device’s status it retrieves to the control center. In this scenario, the update rate is 5 second.