| 8-channel Isolated Analog Voltage Input Module with High Voltage Protection. Communicable over RS-485 and Modbus RTU. Input types include: 0 ~ 500 mV, 0 ~ 1 V, 0 ~ 2.5 V, 0 ~ 5 V, 0 ~ 10 V. |
tM-AD8: $189.00
|
| Please Call 1-888-971-9888 for Volume discount pricing! | |
|
|
The tM-AD8 is an analog input module that includes 8 single-ended analog input channels and provides a programmable input range on all analog inputs (0 ~ 500 mV, 0 ~ 1 V, 0 ~ 2.5 V, 0 ~ 5 V, 0 ~ 10 V). It provides a high overvoltage protection of 120 VDC. The sampling rate of the tM-AD8 is adjustable and is available in either fast or normal mode and It also provides 4 KV ESD protection as well as 2500 Vrms intra-module isolation.
Features
- 8-channel Single-ended Inputs
- Voltage Inputs
- 120 VDC Overvoltage Protection
- Resolution: 14/12 bits
- Adjustable Sampling Rate
- 4 kV ESD and EFT Protecton
- 3 kV Surge Protection
- Dual Watchdog
- 2500 VDC Intra-module Isolation
- Cost-effective
- Wide Operating Temperature Range: -25 °C ~ +75 °C
Applications
- Industrial Automation
- Industrial Machinery
- Building Automation
- Food and Beverage Systems
- Semiconductor Fabrication
- Control Systems
|
| Specifications & Additional Information |
|
| Analog Input |
| Input Channels |
8 Single-ended |
| Type |
0 ~ 500 mV, 0 ~ 1 V, 0 ~ 2.5 V, 0 ~ 5 V, 0 ~ 10 V |
| Resolution |
Normal Mode |
14-bit |
| Fast Mode |
12-bit |
| Sampling Rate |
Normal Mode |
10 Hz total |
| Fast Mode |
200 Hz total |
| Accuracy |
Normal Mode |
+/-0.1% |
| Fast Mode |
+/-0.5% |
| Zero Drift |
+/- 20 μV/°C |
| Span Drift |
+/- 25 ppm/°C |
| Input Impedance |
10 MΩ |
| Overvoltage Protection |
120 VDC |
| Communication |
| Interface |
RS-485 |
| Format |
(N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Baud Rate |
1200 ~ 115200 bps |
| Protocol |
DCON, Modbus/RTU, Modbus/ASCII |
| Dual Watchdog |
Yes, Module (2.3 seconds), Communication (Programmable) |
| LED Indicators |
| Power |
1 LED as Power Indicator |
| Isolation |
| Intra-module Isolation, Field-to-Logic |
2500 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal |
| ±8 kV Air for Random Point |
| EFT (IEC 61000-4-4) |
±4 kV for Power |
| Surge (IEC 61000-4-5) |
±3 kV for Power |
| Power Requirements |
| Reverse Polarity Protection |
Yes |
| Powered from Terminal Block |
Yes, 10 ~ 30 VDC |
| Consumption |
0.6 W Max. |
| Mechanical |
| Dimensions (W x L x H) |
52 mm x 98 mm x 27 mm |
| Installation |
DIN-Rail Mounting |
| Environment |
| Operating Temperature |
-25 °C ~ +75 °C |
| Storage Temperature |
-30 °C ~ +75 °C |
| Humidity |
10 ~ 95% RH, Non-condensing |
|
|
|
I-7514U Isolated 4 Channels RS-485 Active Hub
 More Info |
I-7513 Three-Way Isolated RS-485 to 3 Port RS-485 Hub
 More Info |
I-7561 Windows 7/Vista/XP & Linux USB to RS-232/422/485 Isolated Converter, includes CA-USB18 USB cable
 More Info |
GPSU06U-6 24V/0.25A (max) Power Supply
 More Info |
I-7510 RS-485 Isolated High Speed Repeater
 More Info |
TDS-715 Tiny Serial-to-Ethernet Device Servers with PoE (2-wire RS-485
4-wire RS-422)
 More Info |
tM-AD8C 8-channel Isolated Current Input Module. Communicable over RS-485 and Modbus RTU. Input types include 0-20 mA and 4-20 mA
 More Info |
|
|