We ship via UPS and fastest delivery is with Next Day Air. UPS Next Day Air Early typically gets their product to them as early as 8am, Next Day Air gets their product typically there by 10:30am and Next Day Air Saver typically by 3pm. We ship same day for in stock items and the lead time is up to one week for out of stock items. Delivery is dependent on UPS and your shipping method.
ADD TO CART
ADD TO CART
BUY BY 1-CLICK

Features

I-8084W-G is a 32 bits (hardware) high speed Counter/Frequency/Encoder I/O with "Up Counter", "Frequency", "Up/Down Counter", "Dir/Pulse Counter" and "A/B Phase Counter" mode.

I-8084W-G can has variety mode combination for all 8 channels. That means it can use some channels as "Up Counter" and others as "Frequency" or "A/B Phase".

Features

  • Support 8 Up Counter (Minimum Pulse Width=2 μs).
  • Support 8 Frequency (Minimum Pulse Width=2 μs).
  • Support 4 Up/Down Counter (Minimum Pulse Width=2 μs).
  • Support 4 Dir/Pulse Counter (Minimum Pulse Width=2 μs).
  • Support 4 A/B Phase Counter (Minimum Pulse Width=2 μs).
  • Support 1~32767 (us) digital filter.
  • Support isolated and non-isolated input signals.
  • Equip with Power and Input signal LED indicators.

Applications

Counter measurement, Frequency measurement and Encoder motion control.

Specifications

Digital Input
Mode Counter & Frequency 4-ch Up/Down Counter (CW/CCW)
4-ch Dir/Pulse Counter (Bi-direction)
4-ch A/B Phase (Quadrant Counting)
8-ch Up Counter
8-ch Frequency
Digital Noise Filter 1 ~ 32767 μs
Isolated Input Level On Voltage Level +4.5 VDC ~ +30 VDC
Off Voltage Level +1 VDC Max.
TTL Input Level On Voltage Level +2 VDC ~ +5 VDC
Off Voltage Level 0 VDC ~ +0.8 VDC
Minimum Pulse Width
2 μs Pulse Width
Input Frequency 1 Hz ~ (typically) 250 kHz (both counter mode and frequency mode)
(where 250 kHz is calculated as followings:
supposed that duty cycle = 50%, refer to Minimum Pulse Duration of High Level, we have pulse period = 2 μs x 2 = 4 μs, which is 250 kHz as a maximum)
Maximum Frequency :
refer to Minimum Pulse Duration of High Level, maximum frequency is highly affected by duty cycle
Frequency Accuracy = ± 0.4 %
EEPROM 128 KB
Isolated Voltage 1000 Vrms
ESD Protection 2 kV (Contact for each channel)
LED Display
1 LED as Power Indicator
8 LEDs as Digital Input Indicators
Power
Power Consumption 1 W
Environment
Operating Temperature -25 ~ 75°C
Storage Temperature -30 ~ 85°C
Humidity 5 ~ 95% RH, Non-condensing
Dimensions
30mm x 102mm x 115mm (W x L x H)