M-7011D
1-channel Analog Input, 1-channel Digital Input, and 2-channel Digital Output data acquisition module with display. Supports Thermocouple Input, Voltage Input and Current Input. Communicable over Modbus RTU and RS-485. Supports operating temperatures between -25 to 75°C (-13F ~ 167F).
Features
The M-7011D data acquisition Remote I/O module is a thermocouple input, voltage and current input module. It comes with a LED display, which works as Power/ Communication indicator. It provides cost-effective protection and conditioning for a wide range of valuable industrial control signals and systems. We provide free DCON utility which can help users to configure and test M-7011 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
Specifications
Analog Input | |
Input Channels | 1 |
Input Type | ±15mV, ±50mV, ±100mV,± 500mV , ±1V,± 2.5V ± 20mA (requires optional external 125 ohm resistor) Thermocouple( Type J, K, T, E, R, S, B, N, C) |
Resolution | 16-bit |
Sampling Rate | 10 Samples/ Second |
Accuracy | ±0.05% |
Zero Drift | ±0.5uV/°C |
Span Drift | 25ppm/°C |
Band Width | 5.24Hz |
Common Mode Rejection | 150dB |
Normal Mode Rejection | 100dB |
Input Impedance | 20M Ohms |
Intra-module Isolation, Field to Logic | 3000 VDC |
Digital Input | |
Channels | 1 |
Logic Level 0 | +1V max |
Logic Level 1 | +3.5V to 30V |
Max Input Frequency | 50Hz |
Min. Pulse Width | 1 ms |
Digital Output | |
Channels | 2 |
Output Type | Sink, Open Collector to 30V |
Output Load | 30mA max. per channel |
Power dissipation | 300 mW |
Interface | |
Interface | RS-485 |
Format | N, 8, 1 |
Baudrate | 1200 ~ 115200 bps |
LED Display | |
1 LED | as Power/ Communication indicator |
4 1/2 digits | for I-7011D |
Power | |
Input | +10 to +30 Vdc |
Power Consumption | 0.9 W (I-7011) / 1.5W(I-7011D) |
Protocol | |
Support Modbus and DCON Protocol | Yes |
Watchdog | Yes, Module, Communication (Programmable over DCON) |
Environment | |
Operating temperature | -25°C to 75 °C |
Storage temperature | -30°C to 75 °C |
Humidity | 5 to 95%, non-condensing |
Thermocouple Type | Range (°C) |
J | -210 ~ +760 |
K | -270 ~ +1372 |
T | -270 ~ +400 |
E | -270 ~ +1000 |
R | 0 ~ +1768 |
S | 0 ~ +1768 |
B | 0 ~ +1820 |
N | -270 ~ 1300 |
C | 0 ~ 2320 |