M-7060P
|
|
> Data Acquisition > Remote I/O Modules > M-7000 Remote Data Acquisition Modules via ModBus Protocol > M-7000 Digital data acquisition modules > M-7060P
|
 |
| Product Reference & Support |
|
| 4-channel Isolated DI and 4-channel Relay Output Module with DCON and Modbus Protocol |
M-7060P: $189.00
|
| Please Call 1-888-971-9888 for Volume discount pricing! | |
|
|
- 4 Digital Inputs and 4 Relay Outputs
- Both Form A and Form C Power Relay
- Source and Sink type for DI
- DI Channels Can Be Used As 16-bit Counters
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75 °C
Feature Comparison
| Model Name |
M-7060P |
M-7060 |
| Digital Input |
Max. Input Voltage |
+50 VDC |
+30 VDC |
| Overvoltage Protection |
+/-70 VDC max. |
– |
| Relay Output |
Contact Rating |
16 A @ 250 VAC
10 A @ 30 VDC |
0.3 A @ 250 VAC
2 A @ 30 VDC |
| Surge Strength |
2500 VDC |
500 VDC |
| EMS Protection |
ESD (IEC 61000-4-2) |
+/-4 kV |
– |
| EFT (IEC 61000-4-4) |
+/-4 kV |
– |
| Surge (IEC 61000-4-5) |
+/-3 kV for power liner |
– |
Introduction
The M-7060P offers 4-channel digital inputs, 2-channel Form A power relay outputs and 2-channel Form C power relay outputs at the same time. Moreover, you can choose either sink type or source type of digital input via wire connections. All Input channels are able to be used as 16-bit counters. M-7060P also has 8 LED indicators for power relay outputs and digital inputs status monitoring. And both support the Modbus RTU and DCON protocols which can be confi gured via software. There are options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enrich the noise protection ability for industrial environment. The M-7060P Specifi cations difference, M-7060P It support power relay Form A (16 A @ 250VAC/10 A @ 30 VDC) and Form C (10 A NO/6 A NC @ 250 VAC & 10 A NO/6 A NC @ 30 VDC)
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
|
| Specifications & Additional Information |
|
I/O Specifications
| Relay Output |
| Channel |
4 |
| Type |
Power Relay (Form A × 2, Form C × 2) |
| Contact Rating |
Form A: |
16 A@250 VAC
10 A @ 30 VDC |
| Form C: |
10 A(NO)/6 A(NC) @ 250 VAC |
| Surge Strength |
2500 VDC |
| Operate Time |
6 ms |
| Release Time |
3 ms |
| Mechanical Endurance |
107 ops. |
| Electrical Endurance |
5 × 104 ops. |
| Power-on Value |
Yes |
| Safe Value |
Yes |
| Digital Input/Counter |
| Channel |
4 |
| Contact |
Wet |
| Sink/Source (NPN/PNP) |
Sink/Source |
| On Voltage Level |
+10 ~50 VDC |
| Off Voltage Level |
+4 VDC Max. |
| Counter (100 Hz, 16-bit) |
Yes |
| Input Impedance |
10 kΩ |
| Overvoltage Protection |
+/-70 VDC |
System Specifications
| Communication |
| Interface |
RS-485 |
| Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Baud Rate |
1200 ~ 115200 bps |
| Protocol |
Modbus RTU, DCON |
| Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicator/Display |
| System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
| I/O LED Indicator |
- |
| 7-Segment LED Display |
- |
| Isolation |
| Intra-Module Isolation, Field-to-Logic |
3750 Vrms |
| EMS Protection |
| ESD (IEC 61000-4-2) |
+/-4 kV |
| EFT (IEC 61000-4-4) |
+/-4 kV |
| Surge (IEC 61000-4-5) |
+/- 3 kV |
| Power |
| Reverse Polarity Protection |
Yes |
| Input Range |
10 ~ 30 VDC |
| Consumption |
1.4 W |
| Mechanical |
| Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
| Installation |
DIN-Rail or Wall Mounting |
| Environment |
| Operating Temperature |
-25 ~ +75°C |
| Storage Temperature |
-40 ~ +75°C |
| Humidity |
10 ~ 95% RH, Non-condensing |
|
|
|
DIN-KA52F 24V/1A Power Supply (Din-Rail Mount)
 More Info |
M-7060PD 4-channel Isolated DI and 4-channel Relay Output Module with DCON and Modbus Protocol and LED Display
 More Info |
M-7060 4 Channel Relay Output & 4 Channel Isolated Digital Input Data Acquisition Module communicable over Modbus RTU and RS-485.
 More Info |
M-7060D 4 Channel Relay Output & 4 Channel Isolated Digital Input Data Acquisition Module communicable over Modbus RTU and RS-485 with LED Display
 More Info |
M-7011 Thermocouple Voltage & Current Input Data Acquisition Module with 1 channel communicable over Modbus RTU and RS-485
 More Info |
M-7019R 8 Channel Universal Voltage & Current Input Data Acquisition Current Module with High Voltage Protection communicable over Modbus RTU and RS-485
 More Info |
M-7041 14 Channel Isolated Digital Input Data Acquisition Module, communicable over Modbus RTU and RS-485
 More Info |
M-7050 7 Channel Digital Input and 8 Channel Digital Output Data Acquisition Module communicable over Modbus RTU and RS-485
 More Info |
|
|