- Analog Input
- Input Type: mV, V, mA,Thermocouple
- Input Channels: 8 differential
- Open Thermocouple Detection
- Voltage range:
- ± 15mV, ± 50mV, ± 100mV, ± 150mV, ± 500mV, ± 1V, ± 2.5V, ± 5V, ± 10V
- Current range: ± 20mA (jumper selectable)
- Thermocouple Range :
- Type J, K, T, E, R, S, B, N, C, L, M, L2
- Resolution : 16-bits
- Sampling Rate : 8 samples/second (Total)
- Accuracy : ±0.15%
- -3dB BandWidth : 5.24Hz
- Common Mode Rejection : Typical 86dB
- Voltage Input Impedance : >2M Ω
- Current Impedance = 125 Ω, 1/4w
- Overvoltage Voltage Protection : ±240Vrms
- Individual Channel Configurable
- Wire Opening Detection for Thermocouple
- ESD Protection: 4KV
- Mount: Din Rail Mount
- Communication Interface: RS-485
- Power Supply:
- Input: +10 to +30Vdc
- Consumption :1.2
Thermocouple Type Setting (TT) |
Type
Code |
RTD Type |
|
| 0E |
Type J |
-210 ~ +760 |
| 0F |
Type K |
-270 ~ +1372 |
| 10 |
Type T |
-270 ~ +400 |
| 11 |
Type E |
-270 ~ +1000 |
| 12 |
Type R |
0 ~ +1768 |
| 13 |
Type S |
0 ~ +1768 |
| 14 |
Type B |
0 ~ +1820 |
| 15 |
Type N |
-270 ~ +1300 |
| 16 |
Type C |
0 ~ +2320 |
| 17 |
Type L |
-200 ~ +800 |
| 18 |
Type M |
-200 ~ +100 |
| 19 |
Type L2
(DIN 43710) |
-200 ~ +900 |
|