Analog Input
- Type: mV, V , mA
- (requires optional external 125 ohm resistor)
- Thermocouple:
- Type J, K, T, E, R, S, B, N, C
- Open Thermocouple Detection
- Channels : 10 differential
- Voltage range:
- ±15mV, ± 50mV , ± 100mV,
± 500mV, ± 1V, ± 2.5V
- Current range: ± 20mA
- Sampling rate: 10 Samples/Second
- Bandwidth: 15.7 Hz
- Accuracy: ± 0.1%
- Zero drift: ± 10uV/°C
- CMR @ 50/60 Hz: 86 dB Typical
- NMR @ 50/60 Hz: 100 dB
- Over voltage protection: 240Vrms
- Intra-module Isolation, Field to Logic: 3000VDC
- Photo-Isolation: 3750Vrms
- ±0.3C° Accuracy
Case
- Tests we have conducted show that accuracy is ±0.3C° under certain conditions. These conditions are measurements with type K Thermocouples when ambient temperature is stable and measured temperature is in a narrow range.
- Wire Opening Detection for Thermocouple
- 6KV ESD protection
- Communication Interface:
- Power Supply
- Input: +10 to +30Vdc
- Consumption :1.0W
- Mount
|
Thermocouple type : (C) |
Type |
Range (°C) |
J |
-210 ~ +760 |
K |
-270 ~ +1372 |
T |
-270 ~ +400 |
E |
-270 ~ +1000 |
R |
0 ~ +1768 |
S |
0 ~ +1768 |
B |
0 ~ +1820 |
N |
-270 ~ 1300 |
C |
0 ~ 2320 |
L |
-200 ~ 800
|
M |
-200 ~ 100
|
L (DIN43710) |
-200 ~ 900
|
|